Page B-3
FPU-32 Feeder Protection Unit
Rev.
2-A-103014
Appendix B, FPU-32 Setup Record
P
ARAMETER
A
ND
S
ETTINGS
M
IN
D
EFAULT
M
AX
U
NIT
P
ROGRAM
S
ELECTION
User Register 25
0
0
1399
User Register 26
0
0
1399
User Register 27
0
0
1399
User Register 28
0
0
1399
User Register 29
0
0
1399
User Register 30
0
0
1399
User Register 31
0
0
1399
`
SYSTEM CONFIG
System Name
FPU-32
Password
1111
Password Timeout
1 10.00 60 min
I
2
/I
1
Threshold
0.05 0.50 0.50
UPI LED
None
See Table 4.1 UPI LED Functions
PART II: PROTECTION SET POINTS
F
UNCTION
& S
ET
P
OINT
M
IN
D
EFAUL
T
M
AX
U
NIT
P
ROGRAM
S
ELECTION
Overload – Group1
I
2
t Trip Action
Trip1
Disabled
Trip2
Trip1
Trip3
I
2
t Alarm Action
Alarm1
Disabled
Alarm2
Alarm1
Alarm3
I
2
t Pickup
0.10
1.00
1.25
x I
p
Hot Factor
0.10
0.50
1.00
Cooling Factor
0.10
1.00
10.00
Time Constant
1.00
10.0
60.00
min
I
2
t Alarm level
(Per unit based on 100% I
2
t.)
0.50 0.90 1.00 pu
Overload – Group2
I
2
t Trip Action
Trip1
Disabled
Trip2
Trip1
Trip3
I
2
t Alarm Action
Alarm1
Disabled
Alarm2
Alarm1
Alarm3
I
2
t Pickup
0.10
1.00
1.25
x I
p
Hot Factor
0.10
0.50
1.00
Cooling Factor
0.10
1.00
10.00
Time Constant
1.00
10.0
60.00
min
I
2
t Alarm level
(Per unit based on 100% I
2
t.)
0.50 0.90 1.00 pu
Overload Reset Type
Normal
Normal
Auto
Rapid
Overload Reset Level
0.10 0.30 0.90 pu