Page 3-3
FPU-32 Feeder Protection Unit
Rev.
2-A-103014
System
Wiring
3.2.1.7 RS/EIA/TIA-232 C
OMMUNICATIONS
An RJ-45 TIA-232 connector is provided on the rear
panel of the FPU-32. This port uses the Modbus
RTU
protocol to communicate with SE-Comm-RIS PC-interface
software. For Modbus
RTU protocol, see Appendix C.
The slave ID and communication baud rate are set in the
Setup
Hardware
Local Comms
menu.
Table 3.1 shows the pinout for the optional CA-945
adapter for operation with SE-Comm-RIS. See Fig. 3.1 for
RJ-45 pinout. For a USB connection, use a SE-ICUSB232
adapter.
TABLE 3.1 CA-945 A
DAPTER
N
AME
RJ-45 DB9
RI/DSR 1
9
CD 2 1
DTR 3
4
SG 4
(1)
5
RD 5
(1)
2
TD 6
(1)
3
CTS 7 8
RTS 8 7
(1)
Minimum requirement for communications.
3.2.2 MPU-CIM C
ONNECTIONS
The MPU-CIM CT-input terminal blocks accept 22 to
10 AWG (0.3 to 4.0 mm
2
) conductors. The remaining
MPU-CIM clamping blocks accept 24 to 12 AWG
(0.2 to 2.5mm
2
) conductors.
The MPU-CIM contains four signal-conditioning
interface transformers which are interconnected as shown
in Fig. 3.5. These transformers isolate the FPU-32 from
the phase and earth-fault CT's. The MPU-CIM eliminates
the need for CT shorting contacts when the FPU-32 is
disconnected. Phase-CT and earth-fault-CT secondaries
can be simultaneously grounded through terminal 22 and a
jumper to terminal 20. For applications where the CT
secondaries must be grounded at another location, the CT
secondaries can be isolated by removing shorting screws
A, B, and C through holes in the bottom of the MPU-CIM.
See Figs. 2.3 and 3.5.
N
OTE:
A-B-C phase sequence and polarity must be
observed when connecting phase CT’s. See Section 4.2.1.
Connect the MPU-CIM to the FPU-32 as shown in
Figs. 3.6 and 3.7 using the cable provided with the
MPU-CIM.
TB3
TB2
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
1
R
5
S
E
X
Y
E
F
1
E
F
2
C
O
M
C
B
A
A
B
C
R
S
5
1
R
S
5
1
R
S
5
1
1
2
3
4
5
6
7
8
9
10
11
12
TB1
NOTES:
1. REMOVE SHORTING SCREWS A, B, AND C TO ISOLATE PHASE-CT
AND EARTH-FAULT-CT SECONDARIES FOR IN-LINE APPLICATIONS.
2. SHORTING SCREWS A, B, AND C: 6-32 x 0.375
NICKEL-PLATED-BRASS BINDING HEAD. DO NOT SUBSTITUTE.
3. SHORTING SCREWS A, B, AND C MUST NOT BE REMOVED FOR
RESIDUAL OR TWO-CT CONNECTIONS.
4. EACH TERMINAL ON TB1 AND TB3 WILL ACCEPT ONE
NO. 10 AWG CONDUCTOR.
FIGURE 3.5 MPU-CIM Schematic.