6-4
LY Installation and Maintenance for LY 1001, LY 2001 and LY 3001
LMAIM1501
6.2.2
Single-Phase Motor
NOTE: Your application may vary from the standard wiring configuration for the single-phase motor shown in
Figures 6.3 and 6.4. Refer to the specific actuator wiring diagram for wiring configuration.
1.
Using the Handwheel, move the valve to a midtravel position. Midtravel position allows electrical operation in
the valve “safe” area and keeps the OPEN and CLOSED limit switches from tripping while testing motor
direction.
2.
Momentarily press the OPEN pushbutton to test motor direction. If the actuator moves toward CLOSED,
immediately turn power OFF and proceed with the instructions that match your application. Permanent Split
Capacitor single-phase motors can be connected for opposite rotation by interchanging the leads T1 and T2
coming from the motor to the terminal strip.