
97
INSTALLER SETTING
ENGLISH
Water cooling set temp
Determine cooling setting temperature range when leaving water temperature is selected as
setting temperature.
• In the installer setting list, select water cooling set temp category, and press [OK] button to
move to the detail screen.
* Upper / lower limit / default value is in °C
OK
NOTE
!
Water condensation on the floor
• While cooling operation, it is very important to keep leaving water temperature higher than
16 °C. Otherwise, dew condensation can be occurred on the floor.
• If floor is in humid environment, do not set leaving water temperature below 18 °C.
Value
Default
Range
Max.
24
27~22
Min.
18
20~5
NOTE
!
Water condensation on the radiator
• While cooling operation, cold water may not flow to the radiator. If cold water enters to
the radiator, dew generation on the surface of the radiator can be occurred.