INSTALLATION OF INDOOR UNIT
ENGLISH
Point for attention regarding quality of the public electric power supply
This equipment complies with respectively:
- EN/IEC 61000-3-12 (1) provided that the short-circuit power Ssc is greater than or equal to the
minimum Ssc value at the interface point between the user's supply and the public system. It is
the responsibility of the installer or user of the equipment to ensure, by consultation with the
distribution network operator if necessary, that the equipment is connected only to a supply
with respectively: Ssc greater than or equal to the minimum Ssc value.
- European/International Technical Standard setting the limits for voltage changes, voltage
fluctuations and flicker in public low-voltage supply systems for equipment with rated current
≤
75A.
- European/International Technical Standard setting the limits for harmonic currents produced by
equipment connected to public low-voltage systems with input current
≤
16A of > 75A per
phase.
Circuit Breaker Specification
Perform the electrical wiring work according to
the electrical wiring connection.
- All wiring must comply with local
requirements.
- Select a power source that is capable of
supplying the current required by the air
conditioner.
- Use a recognized ELCB(Electric Leakage
Circuit Breaker) between the power source
and the unit. A disconnection device to
adequately disconnect all supply lines must be fitted.
- Model of circuit breaker recommended by authorized personnel only
Model Name
Minimum Ssc Value
Phase
Capacity
1Ø
5 kW
3,142
7 kW
9 kW
12 kW
14 kW
16 kW
Model Name
Minimum Ssc Value
Phase
Capacity
3Ø
12 kW
2,348
14 kW
16 kW
Indoor
Main
power source
Switch box
ELCB
Outdoor
Model Name
ELCB
Phase
Capacity
1Ø
5 kW
30A
7 kW
9 kW
12 kW
40A
14 kW
16 kW
3Ø
12 kW
20A
14 kW
16 kW