127
INSTALLER SETTING
ENGLISH
Add Zone
Function to set whether or not to use a installed 2nd circuit function using mixing kit.
You can set valve closing time[sec] and hysteresis temperature[°C] on screen by yourself.
Activating this function, It allows 2 zones(Room1, Room2) temperature to be controlled,
separately.
- In case of heating, the temperature of Room1 can not be set higher than Room2 temperature.
- In case of cooling, the temperature of Room1 can not be set lower than Room2 temperature.
Setting range
- Add Zone (2nd Circuit function setting) : Use / Not Use
- Value Closing Time : 60 ~ 999 sec (Default: 240)
- Hysteresis (Thermal On / Off ) : 1 ~ 5 °C (Default: 2)