9. Basic functions
9-10
SV-iC5
9.4 Accel/Decel time and unit setting
Accel/Decel time setting based on Max frequency
Group
LED Display
Parameter Name
Set
Value
Min/Max
Range
Factory
Defaults
Unit
ACC
[Accel time]
-
0/6000 5.0
sec
Drive
group
dEC
[Decel time]
-
0/6000 10.0
sec
Function
group 1
F21 [Max
frequency]
-
0/400
60.0 Hz
H70
[Frequency Reference for
Accel/Decel]
0
0/1 0
Function
group 2
H71
[Accel/Decel Time setting
unit]
- 0/2
1
Set the desired Accel/Decel time at ACC/dEC in Drive group.
If H70 is set to 0 {Max frequency}, Accel/Decel time is the time that takes to reach the max freq from 0 Hz.
Desired Accel/Decel time unit is settable at the H71.
Accel/Decel time is set based on
F21
– [Max frequency]. For instance, if
F21
is set to 60Hz, Accel/Decel
time 5 sec, and run frequency 30Hz, time to reach 30Hz would be 2.5 sec.
Run
command
Run Freq.
30Hz
Accel time
Decel time
Max. freq.
60Hz
Run
command
Reset
Frequency
When H21 is 0
When H21 is 1