11. Monitoring
11-6
SV-iC5
11.5 Multi-function output terminal (MO) and Relay (30AC)
Group
LED
display
Parameter Name
Setting
Factory
default
0
FDT-1
I54
[Multi-function
output terminal
select]
1
FDT-2
2
FDT-3
I55
[Multi-function
relay select]
3
FDT-4
4
FDT-5
5
Overload {OL}
6
Inverter Overload {IOL}
7
Motor stall {STALL}
8
Over voltage trip {OV}
9
Low voltage trip {LV}
10
Inverter heatsink overheat {OH}
11
Command loss
12
During run
13
During stop
14
During constant run
15
During speed searching
16
Wait time for run signal input
17
Fault output
12
I56
[Fault relay output]
When
setting the
H26–
[Number of
auto restart
tries]
When the
trip other
than low
voltage trip
occurs
When the
low voltage
trip occurs
Bit 2
Bit 1
Bit 0
0
- - -
1
- -
2
-
-
3
-
4
- -
5
-
6
-
I/O group
7
2
Select the desired item to be output via MO terminal and relay (30AC).
Summary of Contents for SV-iC5 Series
Page 8: ...Table of Contents viii SV iC5 ...
Page 22: ...3 Wiring 3 6 SV iC5 Notes ...
Page 38: ...5 Programming keypad 5 14 SV iC5 Notes ...
Page 42: ...6 Basic operation 6 4 SV iC5 Notes ...
Page 64: ......
Page 68: ......
Page 108: ...10 Advanced functions 10 20 SV iC5 Notes ...
Page 132: ...13 Troubleshooting Maintenance 13 6 SV iC5 Notes ...
Page 136: ......