9. Basic functions
9-19
SV-iC5
9.7
Frequency
limit
setting
Frequency limit setting based on Max and start frequency
Group
LED display
Parameter name
Set
value
Min/Max
range
Factory
defaults
Unit
F21
[Max frequency]
- 0/400 60.0
Hz
Function
group 1
F23
[Start frequency]
- 0/10 0.5
Hz
Max frequency: Frequency high limit except for F22 [Base frequency]. Any frequency cannot be set above
[Max frequency].
Start frequency: Frequency low limit. If a frequency is set lower than this, 0.00 is automatically set.
Run frequency limit based on frequency High/Low limit
Group
LED Display
Parameter Name
Set
Value
Min/Max
Range
Factory
Defaults
Unit
F24
[Frequency High/Low limit
select]
1
0/1 0
F25
[Frequency high limit]
-
0/400
60.0
Hz
Function
group 1
F26
[Frequency low limit]
-
0/400
0.5
Hz
Set F24 to 1.
Active run frequency can be set within the range set in F25 and F26.
When frequency setting is done via Analog input (voltage or current input), the inverter operates
within the range of high and low limit frequency as shown below.
This setting is also valid when frequency setting is done via keypad.
Freq.
V1(Voltage input)
Max freq.
0
20mA
10V
I (Current input)
High limit
freq.
Low limit
freq.
When freq. limit is not
selected
Summary of Contents for SV-iC5 Series
Page 8: ...Table of Contents viii SV iC5 ...
Page 22: ...3 Wiring 3 6 SV iC5 Notes ...
Page 38: ...5 Programming keypad 5 14 SV iC5 Notes ...
Page 42: ...6 Basic operation 6 4 SV iC5 Notes ...
Page 64: ......
Page 68: ......
Page 108: ...10 Advanced functions 10 20 SV iC5 Notes ...
Page 132: ...13 Troubleshooting Maintenance 13 6 SV iC5 Notes ...
Page 136: ......