9. Basic functions
9-3
SV-iC5
Analog Frequency setting via Voltage analog input (0-10V) or potentiometer on the VR terminal
Group
LED Display
Parameter Name
Set
Value
Min/Max
Range
Factory
Defaults
Unit
0.0 [Frequency
command]
-
-
- Hz
Drive
group
Frq
[Frequency mode]
3
0/8 0
I 6
[Filtering time constant for V1 input]
10
0/9999
10
I 7
[V1 input minimum voltage]
-
0/10
0
V
I 8
[Frequency corresponding to I 7]
-
0/400
0.0
Hz
I 9
[V1 input max voltage]
-
0/10
10
V
I/O group
I10
[Frequency corresponding to I 9]
-
0/400
60.0
Hz
Select
Frq
-[Frequency Mode] to 3 {Frequency setting via V1 terminal}.
The 0-10V input can be directly applied from an external controller or a potentiometer (between VR and CM
terminals).
Wire the terminal as shown below and refer to page 9-2 for I 6 - I10.
Frequency Setting via Analog Current Input (0-20mA)
Group
LED Display
Parameter Name
Set
Value
Min/Max
Range
Factory
Defaults
Unit
0.0 [Frequency
Command]
-
-
- Hz
Drive
group
Frq
[Frequency Mode]
4
0/8 0
I11
[Filtering time constant for I input]
10
0/9999
10
I12
[I input minimum current]
-
0/20
4
mA
I13 [Frequency
corresponding
to I 12]
-
0/400
0.0
Hz
I14
[I input max current]
-
0/20
20
mA
I/O group
I15
[Frequency corresponding to I 14]
-
0/400
60.0
Hz
Select
Frq
– [Frequency Mode] to 4 {Current Analog Input (0-20mA)}.
Frequency is set via 0-20mA input between I and CM terminals.
See page 9-2 for I11-I15.
VR
V1
CM
When connecting potentiometer to
terminals VR and CM
V1
CM
Analog Voltage Input (0-10V)
Summary of Contents for SV-iC5 Series
Page 8: ...Table of Contents viii SV iC5 ...
Page 22: ...3 Wiring 3 6 SV iC5 Notes ...
Page 38: ...5 Programming keypad 5 14 SV iC5 Notes ...
Page 42: ...6 Basic operation 6 4 SV iC5 Notes ...
Page 64: ......
Page 68: ......
Page 108: ...10 Advanced functions 10 20 SV iC5 Notes ...
Page 132: ...13 Troubleshooting Maintenance 13 6 SV iC5 Notes ...
Page 136: ......