7. Function list
7-6
SV-iC5
Function group 1
LED
display
Parameter
name
Min/Max
range
Description
Factory
defaults
Adjustable
during run
Page
F51
4)
[Electronic
thermal level
for 1 minute]
50/200
[%]
This parameter sets max current capable
of flowing to the motor continuously for 1
minute.
The set value is the percentage of H33 –
[Motor rated current].
It cannot be set below F52 –[Electronic
thermal level for continuous].
150 0
F52
[Electronic
thermal level
for continuous]
50/150
[%]
This parameter sets the amount of current
to keep the motor running continuously.
It cannot be set higher than F51 –
[Electronic thermal level for 1 minute].
100 0
0
Standard motor having cooling fan
directly connected to the shaft
F53
[Motor cooling
method]
0/1
1
A motor using a separate motor to
power a cooling fan.
0 0
12-1
F54 [Overload
warning level]
30/150
[%]
This parameter sets the amount of current
to issue an alarm signal at a relay or multi-
function output terminal (see I54, I55).
The set value is the percentage of H33-
[Motor rated current].
150 0
F55 [Overload
warning time]
0/30 [sec]
This parameter issues an alarm signal
when the current greater than F54- [Overload
warning level] flows to the motor for F55-
[Overload warning time].
10 0
12-2
F56 [Overload
trip
select]
0/1
This parameter turns off the inverter output
when motor is overloaded.
1 0
F57 [Overload
trip
level]
30/200
[%]
This parameter sets the amount of
overload current.
The value is the percentage of H33-
[Motor rated current].
180 0
F58 [Overload
trip
time]
0/60 [sec]
This parameter turns off the inverter output
when the F57- [Overload trip level] of current
flows to the motor for F58- [Overload trip
time].
60 0
12-3
4): Set F50 to 1 to display this parameter
Summary of Contents for SV-iC5 Series
Page 8: ...Table of Contents viii SV iC5 ...
Page 22: ...3 Wiring 3 6 SV iC5 Notes ...
Page 38: ...5 Programming keypad 5 14 SV iC5 Notes ...
Page 42: ...6 Basic operation 6 4 SV iC5 Notes ...
Page 64: ......
Page 68: ......
Page 108: ...10 Advanced functions 10 20 SV iC5 Notes ...
Page 132: ...13 Troubleshooting Maintenance 13 6 SV iC5 Notes ...
Page 136: ......