70 | MULTI F OUTDOOR UNIT
Multi F and Multi F MAX Heat Pump System Engineering Manual
MULTI
F
MAX
MULTI
F
Connected Indoor
Units
Combination
Capacity
Index
Outdoor Air
Temp. (°F
DB)
Indoor Air Temp. °F DB / °F WB
68 / 57
73 / 61
77 / 64
80 / 67
86 / 72
90 / 75
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
Two (2) Mixed
Indoor Units
9 + 18
14
18.53
1.01
19.68
1.05
20.83
1.09
21.66
1.10
23.13
1.12
24.28
1.14
20
18.51
1.03
19.66
1.06
20.81
1.10
21.64
1.11
23.11
1.14
24.26
1.16
25
18.50
1.04
19.65
1.08
20.80
1.12
21.63
1.13
23.09
1.15
24.24
1.17
30
18.49
1.05
19.63
1.09
20.78
1.13
21.61
1.15
23.08
1.17
24.23
1.19
35
18.47
1.07
19.62
1.11
20.77
1.15
21.59
1.16
23.06
1.18
24.21
1.21
40
18.46
1.08
19.60
1.12
20.75
1.16
21.58
1.18
23.04
1.20
24.19
1.22
45
18.44
1.10
19.59
1.14
20.73
1.18
21.56
1.19
23.02
1.22
24.17
1.24
50
18.43
1.11
19.57
1.15
20.72
1.20
21.54
1.21
23.01
1.23
24.15
1.26
55
18.41
1.13
19.56
1.17
20.70
1.21
21.53
1.23
22.99
1.25
24.13
1.27
60
18.40
1.14
19.54
1.18
20.69
1.23
21.51
1.24
22.97
1.26
24.11
1.29
65
18.39
1.16
19.53
1.20
20.67
1.24
21.49
1.26
22.95
1.28
24.10
1.31
70
18.37
1.17
19.51
1.21
20.65
1.26
21.48
1.27
22.94
1.30
24.08
1.32
75
17.93
1.23
19.07
1.28
20.21
1.33
21.03
1.34
22.48
1.37
23.62
1.39
80
17.49
1.30
18.62
1.34
19.76
1.39
20.58
1.41
22.03
1.44
23.16
1.47
85
17.05
1.36
18.18
1.41
19.31
1.46
20.13
1.48
21.58
1.51
22.71
1.54
90
16.61
1.42
17.74
1.48
18.87
1.53
19.69
1.55
21.13
1.58
22.26
1.61
95
16.14
1.49
17.26
1.54
18.38
1.60
18.90
1.62
20.63
1.65
21.76
1.68
100
15.74
1.55
16.87
1.61
17.99
1.67
18.66
1.68
20.24
1.72
21.36
1.75
105
15.35
1.61
16.47
1.67
17.60
1.73
18.41
1.75
19.85
1.79
20.97
1.82
110
14.96
1.68
16.08
1.74
17.21
1.80
18.02
1.82
19.45
1.86
20.58
1.89
115
14.56
1.74
15.69
1.80
16.81
1.87
17.62
1.89
19.06
1.93
20.18
1.96
118
14.33
1.78
15.45
1.84
16.58
1.91
17.39
1.93
18.83
1.97
19.95
2.01
122
14.25
1.83
15.37
1.89
16.50
1.96
17.31
1.99
18.75
2.02
19.87
2.06
12 + 15
14
18.53
1.01
19.68
1.05
20.83
1.09
21.66
1.10
23.13
1.12
24.28
1.14
20
18.51
1.03
19.66
1.06
20.81
1.10
21.64
1.11
23.11
1.14
24.26
1.16
25
18.50
1.04
19.65
1.08
20.80
1.12
21.63
1.13
23.09
1.15
24.24
1.17
30
18.49
1.05
19.63
1.09
20.78
1.13
21.61
1.15
23.08
1.17
24.23
1.19
35
18.47
1.07
19.62
1.11
20.77
1.15
21.59
1.16
23.06
1.18
24.21
1.21
40
18.46
1.08
19.60
1.12
20.75
1.16
21.58
1.18
23.04
1.20
24.19
1.22
45
18.44
1.10
19.59
1.14
20.73
1.18
21.56
1.19
23.02
1.22
24.17
1.24
50
18.43
1.11
19.57
1.15
20.72
1.20
21.54
1.21
23.01
1.23
24.15
1.26
55
18.41
1.13
19.56
1.17
20.70
1.21
21.53
1.23
22.99
1.25
24.13
1.27
60
18.40
1.14
19.54
1.18
20.69
1.23
21.51
1.24
22.97
1.26
24.11
1.29
65
18.39
1.16
19.53
1.20
20.67
1.24
21.49
1.26
22.95
1.28
24.10
1.31
70
18.37
1.17
19.51
1.21
20.65
1.26
21.48
1.27
22.94
1.30
24.08
1.32
75
17.93
1.23
19.07
1.28
20.21
1.33
21.03
1.34
22.48
1.37
23.62
1.39
80
17.49
1.30
18.62
1.34
19.76
1.39
20.58
1.41
22.03
1.44
23.16
1.47
85
17.05
1.36
18.18
1.41
19.31
1.46
20.13
1.48
21.58
1.51
22.71
1.54
90
16.61
1.42
17.74
1.48
18.87
1.53
19.69
1.55
21.13
1.58
22.26
1.61
95
16.14
1.49
17.26
1.54
18.38
1.60
18.90
1.62
20.63
1.65
21.76
1.68
100
15.74
1.55
16.87
1.61
17.99
1.67
18.66
1.68
20.24
1.72
21.36
1.75
105
15.35
1.61
16.47
1.67
17.60
1.73
18.41
1.75
19.85
1.79
20.97
1.82
110
14.96
1.68
16.08
1.74
17.21
1.80
18.02
1.82
19.45
1.86
20.58
1.89
115
14.56
1.74
15.69
1.80
16.81
1.87
17.62
1.89
19.06
1.93
20.18
1.96
118
14.33
1.78
15.45
1.84
16.58
1.91
17.39
1.93
18.83
1.97
19.95
2.01
122
14.25
1.83
15.37
1.89
16.50
1.96
17.31
1.99
18.75
2.02
19.87
2.06
Table 63:
LMU24CHV Cooling Capacity Table — Mixed Indoor Units.
TC = Total Capacity (kBtu/h).
PI = Power Input (kW).
Nominal capacity as rated: 0 ft. above sea level with 25 ft. of refrigerant piping.
0 ft. level difference between outdoor and indoor units.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and
67ºF wet bulb (WB), and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
The shaded rows indicate reference data. When operating at this temperature, these values can be
different if the system is not running consistently.
PERFORMANCE DATA
Cooling Capacity Tables