MULTI F OUTDOOR UNIT | 19
Multi F Outdoor Unit Data
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI
F
MAX
MULTI
F
General Data
MULTI F OUTDOOR UNIT
System
Combined With
Rated Cooling
Capacity (Btu/h)
EER
(95°F)
SEER Rated Heating
Capacity (Btu/h)
COP
(47°F)
HSPF
Low Heating
Capacity (Btu/h)
COP
(17°F)
LMU18CHV
Non-Ducted
Indoor Units
17,000
13.0
22.0
22,000
3.2
9.7
13,500
2.4
Ducted Indoor Units
14,000
10.7
17.2
19,800
2.9
9.7
13,000
2.4
Mixed Non-Ducted and
Ducted Indoor Units
15,500
11.8
19.6
20,900
3.0
9.7
13,250
2.4
Table 13: LMU18CHV Efficiency Ratings.
1,2
System
Combined With
Rated Cooling
Capacity (Btu/h)
EER
(95°F)
SEER Rated Heating
Capacity (Btu/h)
COP
(47°F)
HSPF
Low Heating
Capacity (Btu/h)
COP
(17°F)
LMU24CHV
Non-Ducted
Indoor Units
20,000
13.5
21.7
24,000
3.9
10.6
14,500
2.7
Ducted Indoor Units
17,800
11.5
17.5
22,500
3.4
9.8
14,000
2.5
Mixed Non-Ducted and
Ducted Indoor Units
18,900
12.5
19.6
23,250
3.7
10.2
14,250
2.6
System
Combined With
Rated Cooling
Capacity (Btu/h)
EER
(95°F)
SEER Rated Heating
Capacity (Btu/h)
COP
(47°F)
HSPF
Low Heating
Capacity (Btu/h)
COP
(17°F)
LMU36CHV
Non-Ducted
Indoor Units
32,000
13.0
22.0
36,000
3.9
10.0
20,000
2.6
Ducted Indoor Units
28,000
11.0
18.2
34,000
3.5
9.7
19,500
2.4
Mixed Non-Ducted and
Ducted Indoor Units
30,000
12.0
20.1
35,000
3.7
9.9
19,750
2.5
Table 14: LMU24CHV Efficiency Ratings.
1,2,
Table 15: LMU36CHV Efficiency Ratings.
1,2
1
Rated capacity is rated 0 ft. above sea level with 25 ft. of refrigerant line per indoor unit and a 0 ft. level difference between outdoor and indoor units.
All capacities are net with a combination ratio between 95 – 105%.
Rated cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF wet bulb (WB) and outdoor ambient conditions
of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
Rated heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60ºF wet bulb (WB) and outdoor ambient conditions
of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
2
Rated capacity is certified under AHRI Standard 210 / 240. EER, IEER, COP, and HSPF are subject to change. See www.ahrinet.org for the latest
values.