MULTI F OUTDOOR UNIT | 43
Multi F Outdoor Unit Data
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI
F
MAX
MULTI
F
Table 36:
LMU18CHV Cooling Capacity Table — Ducted Indoor Units.
Connected Indoor
Units
Combination
Capacity
Index
Outdoor Air
Temp. (°F
DB)
Indoor Air Temp. °F DB / °F WB
68 / 57
73 / 61
77 / 64
80 / 67
86 / 72
90 / 75
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
Two (2)
Ducted Indoor
Units
9 + 9
14
13.72
0.82
14.58
0.85
15.43
0.88
16.04
0.89
17.13
0.91
17.99
0.92
20
13.71
0.83
14.57
0.86
15.42
0.89
16.03
0.90
17.12
0.92
17.97
0.94
25
13.70
0.84
14.55
0.87
15.41
0.90
16.02
0.92
17.11
0.93
17.96
0.95
30
13.69
0.85
14.54
0.89
15.39
0.92
16.01
0.93
17.09
0.95
17.94
0.96
35
13.68
0.87
14.53
0.90
15.38
0.93
16.00
0.94
17.08
0.96
17.93
0.98
40
13.67
0.88
14.52
0.91
15.37
0.94
15.98
0.95
17.07
0.97
17.92
0.99
45
13.66
0.89
14.51
0.92
15.36
0.96
15.97
0.97
17.06
0.98
17.90
1.00
50
13.65
0.90
14.50
0.93
15.35
0.97
15.96
0.98
17.04
1.00
17.89
1.02
55
13.64
0.91
14.49
0.95
15.33
0.98
15.95
0.99
17.03
1.01
17.88
1.03
60
13.63
0.92
14.48
0.96
15.32
0.99
15.93
1.00
17.02
1.02
17.86
1.04
65
13.62
0.94
14.47
0.97
15.31
1.01
15.92
1.02
17.00
1.04
17.85
1.06
70
13.61
0.95
14.45
0.98
15.30
1.02
15.91
1.03
16.99
1.05
17.83
1.07
75
13.28
1.00
14.12
1.04
14.97
1.07
15.58
1.09
16.65
1.11
17.50
1.13
80
12.95
1.05
13.80
1.09
14.64
1.13
15.24
1.14
16.32
1.16
17.16
1.19
85
12.63
1.10
13.47
1.14
14.31
1.18
14.91
1.20
15.99
1.22
16.82
1.24
90
12.30
1.15
13.14
1.19
13.98
1.24
14.58
1.25
15.65
1.28
16.49
1.30
95
11.95
1.20
12.79
1.25
13.62
1.29
14.00
1.31
15.28
1.33
16.12
1.36
100
11.66
1.25
12.49
1.30
13.33
1.35
13.82
1.36
14.99
1.39
15.82
1.42
105
11.37
1.31
12.20
1.35
13.04
1.40
13.64
1.42
14.70
1.45
15.53
1.47
110
11.08
1.36
11.91
1.41
12.74
1.46
13.35
1.47
14.41
1.50
15.24
1.53
115
10.79
1.41
11.62
1.46
12.45
1.51
13.06
1.53
14.12
1.56
14.95
1.59
118
10.61
1.44
11.45
1.49
12.28
1.55
12.88
1.56
13.94
1.59
14.78
1.62
122
10.56
1.48
11.39
1.53
12.22
1.59
12.82
1.61
13.89
1.64
14.72
1.67
9 + 12
14
13.72
0.82
14.58
0.85
15.43
0.88
16.04
0.89
17.13
0.91
17.99
0.92
20
13.71
0.83
14.57
0.86
15.42
0.89
16.03
0.90
17.12
0.92
17.97
0.94
25
13.70
0.84
14.55
0.87
15.41
0.90
16.02
0.92
17.11
0.93
17.96
0.95
30
13.69
0.85
14.54
0.89
15.39
0.92
16.01
0.93
17.09
0.95
17.94
0.96
35
13.68
0.87
14.53
0.90
15.38
0.93
16.00
0.94
17.08
0.96
17.93
0.98
40
13.67
0.88
14.52
0.91
15.37
0.94
15.98
0.95
17.07
0.97
17.92
0.99
45
13.66
0.89
14.51
0.92
15.36
0.96
15.97
0.97
17.06
0.98
17.90
1.00
50
13.65
0.90
14.50
0.93
15.35
0.97
15.96
0.98
17.04
1.00
17.89
1.02
55
13.64
0.91
14.49
0.95
15.33
0.98
15.95
0.99
17.03
1.01
17.88
1.03
60
13.63
0.92
14.48
0.96
15.32
0.99
15.93
1.00
17.02
1.02
17.86
1.04
65
13.62
0.94
14.47
0.97
15.31
1.01
15.92
1.02
17.00
1.04
17.85
1.06
70
13.61
0.95
14.45
0.98
15.30
1.02
15.91
1.03
16.99
1.05
17.83
1.07
75
13.28
1.00
14.12
1.04
14.97
1.07
15.58
1.09
16.65
1.11
17.50
1.13
80
12.95
1.05
13.80
1.09
14.64
1.13
15.24
1.14
16.32
1.16
17.16
1.19
85
12.63
1.10
13.47
1.14
14.31
1.18
14.91
1.20
15.99
1.22
16.82
1.24
90
12.30
1.15
13.14
1.19
13.98
1.24
14.58
1.25
15.65
1.28
16.49
1.30
95
11.95
1.20
12.79
1.25
13.62
1.29
14.00
1.31
15.28
1.33
16.12
1.36
100
11.66
1.25
12.49
1.30
13.33
1.35
13.82
1.36
14.99
1.39
15.82
1.42
105
11.37
1.31
12.20
1.35
13.04
1.40
13.64
1.42
14.70
1.45
15.53
1.47
110
11.08
1.36
11.91
1.41
12.74
1.46
13.35
1.47
14.41
1.50
15.24
1.53
115
10.79
1.41
11.62
1.46
12.45
1.51
13.06
1.53
14.12
1.56
14.95
1.59
118
10.61
1.44
11.45
1.49
12.28
1.55
12.88
1.56
13.94
1.59
14.78
1.62
122
10.56
1.48
11.39
1.53
12.22
1.59
12.82
1.61
13.89
1.64
14.72
1.67
TC = Total Capacity (kBtu/h).
PI = Power Input (kW).
Nominal capacity as rated: 0 ft. above sea level with 25 ft. of refrigerant piping.
0 ft. level difference between outdoor and indoor units.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and
67ºF wet bulb (WB), and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
The shaded table rows indicate reference data. When operating at this temperature, these values can
be different if the system is not running consistently.
PERFORMANCE DATA
Cooling Capacity Tables