Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
176 | MULTI F OUTDOOR UNIT
Multi F and Multi F MAX Heat Pump System Engineering Manual
MULTI
F
MAX
MULTI
F
Table 169:
LMU36CHV Cooling Capacity Table — Mixed Indoor Units (continued).
Connected Indoor
Units
Combination
Capacity
Index
Outdoor Air
Temp. (°F
DB)
Indoor Air Temp. °F DB / °F WB
68 / 57
73 / 61
77 / 64
80 / 67
86 / 72
90 / 75
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
Four (4) Mixed
Indoor Units
7 + 12 + 12
+ 12
14
29.41
1.57
31.24
1.62
33.06
1.68
34.38
1.70
36.71
1.73
38.54
1.77
20
29.39
1.59
31.21
1.65
33.04
1.71
34.35
1.73
36.69
1.76
38.51
1.79
25
29.36
1.61
31.19
1.67
33.01
1.73
34.33
1.75
36.66
1.78
38.48
1.82
30
29.34
1.63
31.16
1.69
32.99
1.76
34.30
1.78
36.63
1.81
38.45
1.85
35
29.32
1.66
31.14
1.72
32.96
1.78
34.28
1.80
36.60
1.83
38.42
1.87
40
29.30
1.68
31.12
1.74
32.94
1.80
34.25
1.82
36.57
1.86
38.39
1.90
45
29.27
1.70
31.09
1.76
32.91
1.83
34.22
1.85
36.55
1.88
38.36
1.92
50
29.25
1.72
31.07
1.79
32.89
1.85
34.20
1.87
36.52
1.91
38.34
1.95
55
29.23
1.75
31.04
1.81
32.86
1.88
34.17
1.90
36.49
1.93
38.31
1.97
60
29.21
1.77
31.02
1.83
32.83
1.90
34.14
1.92
36.46
1.96
38.28
2.00
65
29.18
1.79
31.00
1.86
32.81
1.92
34.12
1.95
36.43
1.98
38.25
2.02
70
29.16
1.81
30.97
1.88
32.78
1.95
34.09
1.97
36.41
2.01
38.22
2.05
75
28.46
1.91
30.27
1.98
32.07
2.05
33.38
2.08
35.69
2.12
37.49
2.16
80
27.76
2.01
29.56
2.08
31.36
2.16
32.66
2.18
34.97
2.23
36.77
2.27
85
27.06
2.11
28.86
2.18
30.66
2.26
31.96
2.29
34.25
2.33
36.05
2.38
90
26.37
2.21
28.16
2.29
29.95
2.37
31.25
2.40
33.54
2.44
35.33
2.49
95
25.61
2.30
27.40
2.39
29.18
2.47
30.00
2.50
32.75
2.55
34.53
2.60
100
24.99
2.40
26.77
2.49
28.56
2.58
29.61
2.61
32.13
2.66
33.91
2.71
105
24.37
2.50
26.15
2.59
27.93
2.69
29.22
2.72
31.50
2.77
33.29
2.82
110
23.74
2.60
25.53
2.69
27.31
2.79
28.60
2.82
30.88
2.88
32.66
2.93
115
23.12
2.69
24.90
2.79
26.69
2.90
27.98
2.93
30.26
2.98
32.04
3.04
118
22.74
2.75
24.53
2.85
26.31
2.96
27.60
2.99
29.88
3.05
31.67
3.11
122
22.62
2.83
24.40
2.94
26.19
3.04
27.48
3.08
29.76
3.14
31.54
3.20
7 + 7 + 12
+ 18
14
29.41
1.57
31.24
1.62
33.06
1.68
34.38
1.70
36.71
1.73
38.54
1.77
20
29.39
1.59
31.21
1.65
33.04
1.71
34.35
1.73
36.69
1.76
38.51
1.79
25
29.36
1.61
31.19
1.67
33.01
1.73
34.33
1.75
36.66
1.78
38.48
1.82
30
29.34
1.63
31.16
1.69
32.99
1.76
34.30
1.78
36.63
1.81
38.45
1.85
35
29.32
1.66
31.14
1.72
32.96
1.78
34.28
1.80
36.60
1.83
38.42
1.87
40
29.30
1.68
31.12
1.74
32.94
1.80
34.25
1.82
36.57
1.86
38.39
1.90
45
29.27
1.70
31.09
1.76
32.91
1.83
34.22
1.85
36.55
1.88
38.36
1.92
50
29.25
1.72
31.07
1.79
32.89
1.85
34.20
1.87
36.52
1.91
38.34
1.95
55
29.23
1.75
31.04
1.81
32.86
1.88
34.17
1.90
36.49
1.93
38.31
1.97
60
29.21
1.77
31.02
1.83
32.83
1.90
34.14
1.92
36.46
1.96
38.28
2.00
65
29.18
1.79
31.00
1.86
32.81
1.92
34.12
1.95
36.43
1.98
38.25
2.02
70
29.16
1.81
30.97
1.88
32.78
1.95
34.09
1.97
36.41
2.01
38.22
2.05
75
28.46
1.91
30.27
1.98
32.07
2.05
33.38
2.08
35.69
2.12
37.49
2.16
80
27.76
2.01
29.56
2.08
31.36
2.16
32.66
2.18
34.97
2.23
36.77
2.27
85
27.06
2.11
28.86
2.18
30.66
2.26
31.96
2.29
34.25
2.33
36.05
2.38
90
26.37
2.21
28.16
2.29
29.95
2.37
31.25
2.40
33.54
2.44
35.33
2.49
95
25.61
2.30
27.40
2.39
29.18
2.47
30.00
2.50
32.75
2.55
34.53
2.60
100
24.99
2.40
26.77
2.49
28.56
2.58
29.61
2.61
32.13
2.66
33.91
2.71
105
24.37
2.50
26.15
2.59
27.93
2.69
29.22
2.72
31.50
2.77
33.29
2.82
110
23.74
2.60
25.53
2.69
27.31
2.79
28.60
2.82
30.88
2.88
32.66
2.93
115
23.12
2.69
24.90
2.79
26.69
2.90
27.98
2.93
30.26
2.98
32.04
3.04
118
22.74
2.75
24.53
2.85
26.31
2.96
27.60
2.99
29.88
3.05
31.67
3.11
122
22.62
2.83
24.40
2.94
26.19
3.04
27.48
3.08
29.76
3.14
31.54
3.20
TC = Total Capacity (kBtu/h).
PI = Power Input (kW).
Nominal capacity as rated: 0 ft. above sea level with 25 ft. of refrigerant piping.
0 ft. level difference between outdoor and indoor units.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and
67ºF wet bulb (WB), and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
The shaded table columns and rows indicate reference data. When operating at this temperature, these
values can be different if the system is not running consistently.
PERFORMANCE DATA