MULTI F OUTDOOR UNIT | 131
Multi F Outdoor Unit Data
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI
F
MAX
MULTI
F
Table 124:
LMU36CHV Cooling Capacity Table — Ducted Indoor Units (continued).
PERFORMANCE DATA
Cooling Capacity Tables
Connected Indoor
Units
Combination
Capacity
Index
Outdoor Air
Temp. (°F
DB)
Indoor Air Temp. °F DB / °F WB
68 / 57
73 / 61
77 / 64
80 / 67
86 / 72
90 / 75
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
Three (3) Ducted
Indoor Units
9 + 9 + 9
14
23.16
1.49
24.60
1.54
26.04
1.60
27.07
1.62
28.91
1.65
30.35
1.68
20
23.14
1.51
24.58
1.57
26.02
1.62
27.05
1.64
28.89
1.67
30.33
1.71
25
23.12
1.53
24.56
1.59
26.00
1.65
27.03
1.66
28.87
1.70
30.30
1.73
30
23.11
1.55
24.54
1.61
25.98
1.67
27.01
1.69
28.85
1.72
30.28
1.75
35
23.09
1.57
24.52
1.63
25.96
1.69
26.99
1.71
28.82
1.74
30.26
1.78
40
23.07
1.60
24.50
1.65
25.94
1.71
26.97
1.73
28.80
1.77
30.24
1.80
45
23.05
1.62
24.49
1.68
25.92
1.74
26.95
1.76
28.78
1.79
30.21
1.83
50
23.04
1.64
24.47
1.70
25.90
1.76
26.93
1.78
28.76
1.81
30.19
1.85
55
23.02
1.66
24.45
1.72
25.88
1.78
26.91
1.80
28.74
1.84
30.17
1.87
60
23.00
1.68
24.43
1.74
25.86
1.81
26.89
1.83
28.71
1.86
30.14
1.90
65
22.98
1.70
24.41
1.76
25.84
1.83
26.87
1.85
28.69
1.88
30.12
1.92
70
22.97
1.72
24.39
1.79
25.82
1.85
26.85
1.87
28.67
1.91
30.10
1.95
75
22.41
1.82
23.84
1.88
25.26
1.95
26.29
1.97
28.10
2.01
29.53
2.05
80
21.86
1.91
23.28
1.98
24.70
2.05
25.72
2.08
27.54
2.11
28.96
2.16
85
21.31
2.00
22.73
2.08
24.14
2.15
25.17
2.18
26.98
2.22
28.39
2.26
90
20.76
2.10
22.18
2.17
23.59
2.25
24.61
2.28
26.41
2.32
27.83
2.37
95
20.17
2.19
21.58
2.27
22.98
2.35
23.63
2.38
25.79
2.42
27.20
2.47
100
19.68
2.28
21.08
2.37
22.49
2.45
23.32
2.48
25.30
2.53
26.70
2.58
105
19.19
2.38
20.59
2.46
22.00
2.55
23.01
2.58
24.81
2.63
26.21
2.68
110
18.70
2.47
20.10
2.56
21.51
2.65
22.52
2.68
24.32
2.73
25.72
2.79
115
18.21
2.56
19.61
2.65
21.02
2.75
22.03
2.78
23.83
2.84
25.23
2.89
118
17.91
2.62
19.32
2.71
20.72
2.81
21.74
2.84
23.53
2.90
24.94
2.96
122
17.81
2.69
19.22
2.79
20.62
2.89
21.64
2.92
23.43
2.98
24.84
3.04
9 + 9 + 12
14
25.73
1.59
27.33
1.65
28.93
1.71
30.08
1.73
32.13
1.76
33.72
1.80
20
25.71
1.62
27.31
1.67
28.91
1.74
30.06
1.76
32.10
1.79
33.70
1.82
25
25.69
1.64
27.29
1.70
28.88
1.76
30.04
1.78
32.08
1.81
33.67
1.85
30
25.67
1.66
27.27
1.72
28.86
1.78
30.01
1.80
32.05
1.84
33.65
1.88
35
25.65
1.68
27.25
1.75
28.84
1.81
29.99
1.83
32.03
1.86
33.62
1.90
40
25.63
1.71
27.23
1.77
28.82
1.83
29.97
1.85
32.00
1.89
33.59
1.93
45
25.62
1.73
27.21
1.79
28.80
1.86
29.95
1.88
31.98
1.91
33.57
1.95
50
25.60
1.75
27.19
1.82
28.77
1.88
29.92
1.90
31.95
1.94
33.54
1.98
55
25.58
1.78
27.16
1.84
28.75
1.91
29.90
1.93
31.93
1.97
33.52
2.00
60
25.56
1.80
27.14
1.86
28.73
1.93
29.88
1.95
31.90
1.99
33.49
2.03
65
25.54
1.82
27.12
1.89
28.71
1.96
29.85
1.98
31.88
2.02
33.47
2.06
70
25.52
1.84
27.10
1.91
28.69
1.98
29.83
2.00
31.86
2.04
33.44
2.08
75
24.90
1.94
26.48
2.01
28.06
2.09
29.21
2.11
31.23
2.15
32.81
2.19
80
24.29
2.04
25.87
2.12
27.44
2.19
28.58
2.22
30.60
2.26
32.17
2.31
85
23.68
2.14
25.25
2.22
26.83
2.30
27.96
2.33
29.97
2.37
31.55
2.42
90
23.07
2.24
24.64
2.32
26.21
2.41
27.34
2.44
29.35
2.48
30.92
2.53
95
22.41
2.34
23.97
2.43
25.53
2.52
26.25
2.54
28.66
2.59
30.22
2.64
100
21.87
2.44
23.43
2.53
24.99
2.62
25.91
2.65
28.11
2.70
29.67
2.76
105
21.32
2.54
22.88
2.63
24.44
2.73
25.57
2.76
27.56
2.81
29.13
2.87
110
20.77
2.64
22.34
2.74
23.90
2.84
25.02
2.87
27.02
2.92
28.58
2.98
115
20.23
2.74
21.79
2.84
23.35
2.94
24.48
2.98
26.47
3.03
28.03
3.09
118
19.90
2.80
21.46
2.90
23.02
3.01
24.15
3.04
26.15
3.10
27.71
3.16
122
19.79
2.88
21.35
2.98
22.91
3.09
24.04
3.13
26.04
3.19
27.60
3.25
TC = Total Capacity (kBtu/h).
PI = Power Input (kW).
Nominal capacity as rated: 0 ft. above sea level with 25 ft. of refrigerant piping.
0 ft. level difference between outdoor and indoor units.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and
67ºF wet bulb (WB), and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
The shaded table rows indicate reference data. When operating at this temperature, these values can
be different if the system is not running consistently.