MULTI F OUTDOOR UNIT | 137
Multi F Outdoor Unit Data
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI
F
MAX
MULTI
F
Connected Indoor
Units
Combination
Capacity
Index
Outdoor Air
Temp. (°F
DB)
Indoor Air Temp. °F DB / °F WB
68 / 57
73 / 61
77 / 64
80 / 67
86 / 72
90 / 75
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
Four (4) Ducted
Indoor Units
9 + 9 + 9
+ 18
14
27.45
1.59
29.15
1.65
30.86
1.71
32.09
1.73
34.27
1.76
35.97
1.80
20
27.43
1.62
29.13
1.67
30.83
1.74
32.06
1.76
34.24
1.79
35.94
1.82
25
27.41
1.64
29.11
1.70
30.81
1.76
32.04
1.78
34.21
1.81
35.92
1.85
30
27.39
1.66
29.09
1.72
30.79
1.79
32.02
1.81
34.19
1.84
35.89
1.88
35
27.36
1.68
29.06
1.75
30.76
1.81
31.99
1.83
34.16
1.86
35.86
1.90
40
27.34
1.71
29.04
1.77
30.74
1.83
31.97
1.86
34.14
1.89
35.83
1.93
45
27.32
1.73
29.02
1.79
30.72
1.86
31.94
1.88
34.11
1.92
35.81
1.95
50
27.30
1.75
29.00
1.82
30.69
1.88
31.92
1.91
34.08
1.94
35.78
1.98
55
27.28
1.78
28.98
1.84
30.67
1.91
31.89
1.93
34.06
1.97
35.75
2.01
60
27.26
1.80
28.95
1.86
30.65
1.93
31.87
1.95
34.03
1.99
35.72
2.03
65
27.24
1.82
28.93
1.89
30.62
1.96
31.84
1.98
34.01
2.02
35.70
2.06
70
27.22
1.84
28.91
1.91
30.60
1.98
31.82
2.00
33.98
2.04
35.67
2.08
75
26.56
1.94
28.25
2.02
29.94
2.09
31.15
2.11
33.31
2.15
34.99
2.20
80
25.91
2.04
27.59
2.12
29.27
2.20
30.49
2.22
32.64
2.26
34.32
2.31
85
25.26
2.14
26.94
2.22
28.61
2.30
29.83
2.33
31.97
2.37
33.65
2.42
90
24.61
2.24
26.28
2.32
27.96
2.41
29.17
2.44
31.30
2.48
32.98
2.53
95
23.91
2.34
25.57
2.43
27.24
2.52
28.00
2.55
30.57
2.59
32.23
2.65
100
23.32
2.44
24.99
2.53
26.65
2.62
27.64
2.65
29.98
2.70
31.65
2.76
105
22.74
2.54
24.41
2.63
26.07
2.73
27.27
2.76
29.40
2.81
31.07
2.87
110
22.16
2.64
23.82
2.74
25.49
2.84
26.69
2.87
28.82
2.92
30.49
2.98
115
21.58
2.74
23.24
2.84
24.91
2.94
26.11
2.98
28.24
3.03
29.90
3.09
118
21.23
2.80
22.89
2.90
24.56
3.01
25.76
3.04
27.89
3.10
29.55
3.16
122
21.11
2.88
22.78
2.98
24.44
3.09
25.64
3.13
27.77
3.19
29.44
3.25
9 + 12 + 12
+ 12
14
27.45
1.59
29.15
1.65
30.86
1.71
32.09
1.73
34.27
1.76
35.97
1.80
20
27.43
1.62
29.13
1.67
30.83
1.74
32.06
1.76
34.24
1.79
35.94
1.82
25
27.41
1.64
29.11
1.70
30.81
1.76
32.04
1.78
34.21
1.81
35.92
1.85
30
27.39
1.66
29.09
1.72
30.79
1.79
32.02
1.81
34.19
1.84
35.89
1.88
35
27.36
1.68
29.06
1.75
30.76
1.81
31.99
1.83
34.16
1.86
35.86
1.90
40
27.34
1.71
29.04
1.77
30.74
1.83
31.97
1.86
34.14
1.89
35.83
1.93
45
27.32
1.73
29.02
1.79
30.72
1.86
31.94
1.88
34.11
1.92
35.81
1.95
50
27.30
1.75
29.00
1.82
30.69
1.88
31.92
1.91
34.08
1.94
35.78
1.98
55
27.28
1.78
28.98
1.84
30.67
1.91
31.89
1.93
34.06
1.97
35.75
2.01
60
27.26
1.80
28.95
1.86
30.65
1.93
31.87
1.95
34.03
1.99
35.72
2.03
65
27.24
1.82
28.93
1.89
30.62
1.96
31.84
1.98
34.01
2.02
35.70
2.06
70
27.22
1.84
28.91
1.91
30.60
1.98
31.82
2.00
33.98
2.04
35.67
2.08
75
26.56
1.94
28.25
2.02
29.94
2.09
31.15
2.11
33.31
2.15
34.99
2.20
80
25.91
2.04
27.59
2.12
29.27
2.20
30.49
2.22
32.64
2.26
34.32
2.31
85
25.26
2.14
26.94
2.22
28.61
2.30
29.83
2.33
31.97
2.37
33.65
2.42
90
24.61
2.24
26.28
2.32
27.96
2.41
29.17
2.44
31.30
2.48
32.98
2.53
95
23.91
2.34
25.57
2.43
27.24
2.52
28.00
2.55
30.57
2.59
32.23
2.65
100
23.32
2.44
24.99
2.53
26.65
2.62
27.64
2.65
29.98
2.70
31.65
2.76
105
22.74
2.54
24.41
2.63
26.07
2.73
27.27
2.76
29.40
2.81
31.07
2.87
110
22.16
2.64
23.82
2.74
25.49
2.84
26.69
2.87
28.82
2.92
30.49
2.98
115
21.58
2.74
23.24
2.84
24.91
2.94
26.11
2.98
28.24
3.03
29.90
3.09
118
21.23
2.80
22.89
2.90
24.56
3.01
25.76
3.04
27.89
3.10
29.55
3.16
122
21.11
2.88
22.78
2.98
24.44
3.09
25.64
3.13
27.77
3.19
29.44
3.25
Table 130:
LMU36CHV Cooling Capacity Table — Ducted Indoor Units (continued).
TC = Total Capacity (kBtu/h).
PI = Power Input (kW).
Nominal capacity as rated: 0 ft. above sea level with 25 ft. of refrigerant piping.
0 ft. level difference between outdoor and indoor units.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and
67ºF wet bulb (WB), and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
The shaded table rows indicate reference data. When operating at this temperature, these values can
be different if the system is not running consistently.
PERFORMANCE DATA
Cooling Capacity Tables