Electrical System Installation
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Power Wiring and Communication Cable Terminations
ELECTRICAL
Internal Routing and Terminations in Large Frame Outdoor Units.
Close Up of Wiring / Cable Connections in Large Frame Outdoor Units.
Main Power Wiring Connection
Communication Cable / Ground Wiring Connections
Main Power
Terminal Block
Insulation Sleeve
Attachments
Ground Wiring
Master Outdoor Unit to
Slave Outdoor Unit
Communication Cable
Outdoor Unit to Indoor Unit
Communication Cable
Ground Wiring
Power Wiring / Communication Cable Routed Through the Front
Power Wiring / Communication Cable
Routed Through the Bottom (Left)
Main Power
Terminal Block
Ground Wire
When Connecting Communication
Cable / Ground Wire through
Front Panel
Gap between Power Wiring and
Communication Cable must be
≥
2 inches.
Attach firmly with a cable tie or clamp cord.
When Connecting Main Power
Wiring / Ground Wire through
Front Panel
Main Power Terminal Block
Ground Wire
Gap between Power Wiring
and Communication Cable
must be
≥
2 inches.
When Connecting Main Power Wiring /
Ground Wire through Bottom Left Side
When Connecting Communication Cable /
Ground Wire through Front Panel
Position the power wiring /
communication cables so that
electromagnetic interference with
the oil level sensor is avoided.
If the oil sensor is subjected to
electromagnetic interference, it
may malfunction.