ELECTRICAL
Location of Outdoor Unit PCBs and Other Electrical Components
Main Board
External Board
Main Power Wiring
Terminal Block
Small Frame Outdoor Units
Large Frame Outdoor Units
(Connect the three (3) wires
properly for the three (3)
phase wiring system.)
Outdoor Unit Electrical Component Locations.
Power Wiring and Communication Cable Terminations
Internal Routing and Terminations in Small Frame Outdoor Units.
Main Power
Terminal Block
Insulation Sleeve
Attachments
Main Power Wiring Connection
Communication Cable / Ground Wiring Connections
Ground Wiring
Master Outdoor Unit to
Slave Outdoor Unit
Communication Cable
Outdoor Unit to Indoor Unit
Communication Cable
Ground Wiring
Main Power Terminal Block
Ground Wire
When Connecting Communication Cable /
Ground Wire through Front Panel
Gap between Power Wiring
and Communication Cable
must be
≥
2 inches.
Power Wiring / Communication Cable Routed Through the Front
Attach firmly with a cable tie or clamp cord.
When Connecting Main Power Wiring /
Ground Wire through Front Panel
Power Wiring / Communication Cable Routed Through the Bottom (Left)
Main Power Terminal Block
Ground Wire
Gap between Power Wiring
and Communication Cable
must be
≥
2 inches.
When Connecting Main Power Wiring /
Ground Wire through Bottom Left Side
When Connecting Communication Cable /
Ground Wire through Front Panel
Close Up of Wiring / Cable Connections in Small Frame Outdoor Units.
Position the power wiring /
communication cables so that
electromagnetic interference with
the oil level sensor is avoided.
If the oil sensor is subjected to
electromagnetic interference, it
may malfunction.