74
MUL
TI V 5 Outdoor Unit Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
INSTALLING FOR HEAT RECOVERY
OPERATION
Heat Recovery Units
Model
PRHR022A
PRHR032A
PRHR042A
Number of Ports
2
3
4
Max. Connectible No. of Indoor Units
16
24
32
Max. Connectible No. of Indoor Units on each port
8
8
8
Max. Port Capacity (each port)
Btu/h
54,000
54,000
54,000
Max. Unit Capacity (sum of ports)
Btu/h
192,000
192,000
192,000
Net Weight
lbs.
40
45
49
Dimensions (W x H x D)
inches
17-7/8 x 8-5/8 x 18-15/16
Casing
Galvanized steel plate
Connecting Pipes
To Indoor Units
Liquid Pipe (inches)
3/8
Vapor Pipe (inches)
5/8
To Outdoor Units
Liquid (inches)
3/8
1/2
5/8
Low-pressure Vapor (inches)
7/8
1-1/8
1-1/8
High-pressure Vapor (inches)
3/4
7/8
7/8
Insulation Material
Polyethylene
Current
Minimum Circuit Amps (MCA)
0.1
0.15
0.2
Maximum Fuse Amps (MFA)
15
Power Supply
1Ø, 208-230V, 60Hz
Heat recovery units are REQUIRED for systems that are designed for heat recovery operation. Heat recovery units can ONLY be used with LG
systems designed for heat recovery operation that include liquid, low pressure vapor, and high pressure vapor refrigerant pipes.
Table 35:
Heat Recovery Unit Specifications.
Unit Model No.
V / Hz / Ph
Input (kW)
Cooling
Heating
PRHR022A
208-230 / 60 / 1
0.026
0.026
PRHR032A
208-230 / 60 / 1
0.033
0.033
PRHR042A
208-230 / 60 / 1
0.040
0.040
Table 36: Heat Recovery Unit Electrical Data.