TI V 5 Outdoor Unit Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Model
PRHR022A
PRHR032A
PRHR042A
Number of Ports
2
3
4
Connecting Pipes
To Indoor Units
Liquid Pipe (inches)
3/8
Vapor Pipe (inches)
5/8
To Outdoor Units
Liquid (inches)
3/8
1/2
5/8
Low-pressure Vapor (inches)
7/8
1-1/8
1-1/8
High-pressure Vapor (inches)
3/4
7/8
7/8
INSTALLING FOR HEAT RECOVERY
OPERATION
Heat Recovery Units
1. Series connection of heat recovery units: Total
capacity of indoor units ≤192,000 Btu/h.
2. Refer to the heat recovery unit PCB for valve group
control setting.
3. Maximum capacity of each port is 54,000 Btu/h and
eight (8) indoor units.
4.
Do not skip ports when connecting indoor
units. Start at port 1, then use 2, then use 3, then
use 4 (the numbers are displayed on the heat
recovery ports).
Vapor Pipe Ø5/8, Liquid Pipe Ø3/8
Brazed Connections
1 2
3 4
Remove Caps Before
Brazing
Liquid Pipe
Low Pressure Vapor Pipe
High Pressure Vapor Pipe
Close Up of the Heat Recovery Unit Connections.
Heat Recovery Unit Connections and Limitations
Table 37: Heat Recovery Unit Piping Connection Sizes.
Removing the Caps
Before brazing the field-supplied refrigerant piping to the heat recovery unit connections, the caps MUST be removed from the liquid, high
pressure vapor, and low pressure vapor pipe connections.
Removing the caps releases any gas present in the heat recovery unit. If the gas isn’t released, physical injury or death may occur from the uncon-
trolled rapid release of gas, or if the gas comes in contact with a flare during brazing and generates a poisonous gas.
Piping Connection Options
Heat recovery units can connect to the field-supplied refrigerant piping on the left side or on the right side. Heat recovery units can also be
installed in series / in parallel using these side connections.
Pipe Connection from Left Side
Series / Parallel Pipe Connection
Pipe Connection from Right Side
Heat Recovery Unit Piping Connection Options.
On whichever port or pipe not used, the factory-provided cap must be removed, and that port / pipe must be recapped and insulated.