Setting the Optional Modes
Static Pressure Compensation
Function (Fn2)
Static Pressure Compensation function modifies the maximum out-
door unit fan speed during normal system operation. Use to raise the
maximum outdoor unit fan speed to compensate for an obstruction
(duct) in airflow.
The default outdoor fan external static pressure rating for Multi V 5
Outdoor Units is 0.16 in-wg. Selecting “op3” raises the fan speed to
produce the same airflow at 0.32 in-wg.
Refer to the Multi V Engineering Manuals for the default static
pressure rating, and the maximum static pressure rating with this
function engaged.
For use on both heat pump and heat recovery systems.
Table 47: Setting Static Pressure Compensation Function.
Turn No. 5 on the master outdoor unit PCB
DIP switch bank SW01 to ON.
Select the “Func” mode by using the SW03C forward ►button and the
SW02C backward ◄ button, and then press the SW01C confirm
● button.
Select the “Fn2” function by using the SW03C forward ►button and
the SW02C backward ◄ button, and then press the SW01C
confirm ● button.
Select from “oFF”, “op1” through “op3” options (see table) by using the
SW03C forward ►button and the SW02C backward ◄ button,
and then press the SW01C confirm ● button.
Press the SW01D Reset Button one (1) time to reset PCB.
The selected option value is saved in the EPROM.
Setting the Static Pressure Compensation Function.
• Ask a trained LG service provider to set this function during system
installation.
• If the outdoor unit RPM is changed, cooling capacity may be
reduced.
Settings
Nominal 6 Ton (RPM)
ESP (in-wg)
Nominal 8 to 20 Ton (RPM)
ESP (in-wg)
oFF (Default)
880
0.16
1,000
0.16
op1
910
0.231
1,040
0.25*
op2
930
0.271
1,070
0.27*
op3
950
0.32
1,100
0.32
*Settings “op1” and “op2” are interpolated externals static pressure values given the values for “oFF” and “op3”.
PRE-COMMISSIONING