Wall Mounted Unit (4)
2. Specifications
Model Name
ZJNW30GRLA1
[US30F NR0]
ZJNW36GRLA1
[US36F NR0]
Power Supply
V, Ø, Hz
220-240, 1, 50
220-240, 1, 50
220, 1, 60
220, 1, 60
Power Input
H / M / L
W
47 / 42 / 36
65 / 47 / 42
Running Current
H / M / L
A
0.32 / 0.28 / 0.25
0.43 / 0.32 / 0.28
Max.
A
0.90
0.90
Casing Color(RAL)
-
Magic White(9016)
Magic White(9016)
Dimensions
Body
W x H x D
mm
1,200 x 360 x 265
1,200 x 360 x 265
W x H x D
inch
47-1/4 × 14-3/16 × 10-7/16
47-1/4 × 14-3/16 × 10-7/16
Shipping
W x H x D
mm
1,280 x 360 x 455
1,280 x 360 x 455
W x H x D
inch
50-13/32 × 14-3/16 × 17-29/32
50-13/32 × 14-3/16 × 17-29/32
Weight
Body
kg (lbs)
18.3
18.3
Shipping
kg (lbs)
22.9
22.9
Heat Exchanger
(Row x Column x Fins per inch) x
No.
-
(3 x 18 x 21) x 1
(3 x 18 x 21) x 1
Face Area
m
2
(ft
2
)
0.35
0.35
Fan
Type
-
Cross Flow Fan
Cross Flow Fan
Air Flow Rate
H / M / L
m
3
/min
21.0 / 17.0 / 13.0
25.0 / 21.0 / 17.0
H / M / L
ft
3
/min
742 / 600 / 459
883 / 742 / 600
Fan Motor
Type
-
BLDC
BLDC
Output
W x No.
113 x 1
113 x 1
Sound Pressure
Level
Cooling
H / M / L
dB(A)
46 / 42 / 38
51 / 46 / 42
Heating
H / M / L
dB(A)
46 / 42 / 38
51 / 46 / 42
Sound Power Level
Cooling
Rated
dB(A)
62
65
Heating
Rated
dB(A)
-
-
Piping Connections
Liquid
mm(inch)
Φ9.52 (3/8)
Φ9.52 (3/8)
Gas
mm(inch)
Φ15.88 (5/8)
Φ15.88 (5/8)
Drain
O.D. / I.D.
mm
Φ 16.5 / 14.5
Φ 16.5 / 14.5
Safety Devices
-
Fuse
Fuse
-
Thermal Protector for Fan Motor Thermal Protector for Fan Motor
Connections Method
-
Flared
Flared
Power and Communication Cable (included Earth)
No. x mm
2
(AWG)
4C x 0.75 (18)
4C x 0.75 (18)
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national code. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound Level Values are measured at Noise Measuring chamber accordance with standard. Therefore, these values depend on the ambient conditions
and values are normally higher in actual operation(Sound Pressure : LG Internal standard, Sound Power : EN 12102 (ISO 3741).
4. Capacities are net capacities and based on the following conditions. Refer to the Outdoor Unit Specifications for calculating the real capacity.
• Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
• Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
• Interconnected Pipe is standard length and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.