2. Specifications
11
MULTI/SINGLE
Indoor unit
Wall Mounted Unit (1)
̰
Standard plus
Model Name
AMNW05GSJB0
[PM05SP NSJ]
AMNW07GSJB0
[PM07SP NSJ]
Power Supply
V, Ø, Hz
220-240, 1, 50
220-240, 1, 50
220, 1, 60
220, 1, 60
Capacity
Cooling
kW
1.5
2.1
Heating
kW
1.6
2.3
Power Input
Min./Nom./Max.
W
11 / 16 / 30
11 / 17 / 30
Running Current
Min./Nom./Max.
A
0.10 / 0.13 / 0.20
0.10 / 0.14 / 0.20
Casing Color
-
Munsell 7.5BG 10/2 (RAL 9016)
Dimensions
Body
W x H x D
mm
837 × 308 × 189
837 × 308 × 189
W x H x D
inch
32-15/16 x 12-1/8 x 7-7/16
32-15/16 x 12-1/8 x 7-7/16
Shipping
W x H x D
mm
909 x 383 x 256
909 x 383 x 256
W x H x D
inch
35-25/32 x 15-3/32 x 10-3/32
35-25/32 x 15-3/32 x 10-3/32
Weight
Body
kg (lbs)
8.7 (19.2)
8.7 (19.2)
Shipping
kg (lbs)
12.0 (26.5)
12.0 (26.5)
Heat Exchanger
(Row x Column x Fins per inch) x
No.
-
(2 x 15 x 21) x 1
(2 x 15 x 21) x 1
Face Area
m
2
(ft
2
)
0.19 (2.05)
0.19 (2.05)
Fan
Type
-
Cross Flow Fan
Cross Flow Fan
Air Flow Rate
H / M / L
m
3
/min
8.3 / 6.7 / 5.6
8.6 / 7.2 / 5.6
H / M / L
ft
3
/min
293 / 237 / 198
304 / 254 / 198
Fan Motor
Type
-
BLDC
BLDC
Output
W x No.
30 x 1
30 x 1
Sound Pressure Level
H / M / L
dB(A)
34 / 31 / 27
35 / 32 / 27
Sound Power Level
Rated
dB(A)
57
57
Piping Connections
Liquid
mm(inch)
Ø 6.35 (1/4)
Ø 6.35 (1/4)
Gas
mm(inch)
Ø 9.52 (3/8)
Ø 9.52 (3/8)
Drain
O.D. / I.D.
mm
Ø 21.5 / 16.0
Ø 21.5 / 16.0
Safety Devices
-
Fuse
-
Thermal Protector for Fan Motor
Connections Method
-
Flared
Flared
Power and Communication Cable (included Earth)
No. x mm
2
(AWG)
4C x 0.75 (18)
4C x 0.75 (18)
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national code. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound Level Values are measured at Noise Measuring chamber accordance with standard. Therefore, these values depend on the ambient conditions
and values are normally higher in actual operation(Sound Pressure : LG Internal standard, Sound Power : EN 12102 (ISO 3741).
4. Capacities are net capacities and based on the following conditions. Refer to the Outdoor Unit Specifications for calculating the real capacity.
• Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
• Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
• Interconnected Pipe is standard length and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.