MULTI/SINGLE
Indoor unit
8. Installation
44
Wall Mounted Unit (1)
CAUTION
If the drain hose is routed inside the room insulate the hose with an insulation material* so that dripping from
sweating condensation) will not damage furniture or floors.
* Foamed polyethylene or equivalent is recommended.
CAUTION
•
Press on the tubing cover and unfold the tubing to downward slowly. And then bend to the left side
slowly.
•
Following bending case from right to left directly may cause damage to the tubing.
• Installation Information. For right piping. Follow the instruction above.
8.2.2 Installation of Indoor Unit
̰
Seat the indoor unit on the installation plate
1. Hook the indoor unit onto the upper portion of the installation plate.(engage the three hooks at the top of the
indoor unit with the upper edge of the installation plate) Ensure that the hooks areproperly seated on the
installation plate by moving it left and right
2. Unlock the tubing holder from the chassis and mount between the chassis and installation plate in order to
separate the bottom side of the indoor unit from the wall.
Insulation material
Vinyl tape(narrow)
Connection pipe
Connecting cable
Vinyl tape (wide)
Wrap with vinyl tape
Indoor unit pipe
Pipe
Gas Pipe
Liquid Pipe
Cutting Line
Cutting Line
Good Case
Bad Case
* Tubing cutting line have to be upward.
ೈ
The feature can be changed according to type