4
MULTI/SINGLE CAC
Indoor unit
Ceiling Mounted cassette 1-way
2. Specifications
Model Name
ZMNW09GTUA0
[MT09R NU1]
ZMNW12GTUA0
[MT11R NU1]
Power Supply
V, Ø, Hz
220-240, 1, 50
220-240, 1, 50
220, 1, 60
220, 1, 60
Power Input
W x No.
20 × 1
20 × 1
Running Current
A
0.2
0.2
Casing Color
-
-
-
Dimensions
Body
W x H x D
mm
860 × 132 × 450
860 × 132 × 450
W x H x D
inch
33-27/32 x 5-3/16 x
17-23/32
33-27/32 x 5-3/16 x
17-23/32
Net Weight
Body
kg (lbs)
11.7 (25.8)
11.7 (25.8)
Heat Exchanger
(Row x Column x Fins per inch) x No.
-
(2 x 12 x 18) x 1
(2 x 12 x 18) x 1
Face Area
m
2
(ft
2
)
0.18 (1.90)
0.18 (1.90)
Fan
Type
-
Cross Flow Fan
Cross Flow Fan
Air Flow Rate
H / M / L
m
3
/min
7.5 / 7.3 / 6.8
8.1 / 7.4 / 7.0
H / M / L
ft
3
/min
265 / 258 / 240
286 / 261 / 247
Fan Motor
Type
-
BLDC
BLDC
Output
W x No.
20 x 1
20 x 1
Sound Pressure Level
H / M / L
dB(A)
36 / 34 / 32
37 / 36 / 33
Sound Power Level
Rated
dB(A)
54
57
Piping Connections
Liquid
mm(inch)
Ø 6.35 (1/4)
Ø 6.35 (1/4)
Gas
mm(inch)
Ø 9.52 (3/8)
Ø 9.52 (3/8)
Drain (O.D. / I.D.)
mm
Ø 32.0 / 25.0
Ø 32.0 / 25.0
Safety Devices
-
Fuse
-
Thermal Protector for Fan Motor
Power and Communication Cable (included Earth)
No. x mm
2
(AWG)
4C x 0.75 (18)
4C x 0.75 (18)
Decoration Panel
Model Name
-
PT-UUC1
PT-UUC1
Casing Color
-
Morning Fog
Morning Fog
Dimensions
W x H x D
mm
1,100 × 34 × 500
1,100 × 34 × 500
W x H x D
inch
43-5/16 x 1-11/32 x
19-11/16
43-5/16 x 1-11/32 x
19-11/16
Net weight
kg (lbs)
4.4(9.7)
4.4(9.7)
Note
1. Due to our policy of innovation some specifications may be changed without notification.
2. Wiring cable size must comply with the applicable local and national code. And “Electric characteristics” chapter should be considered for electrical
work and design. Especially the power cable and circuit breaker should be selected in accordance with that.
3. Sound Level Values are measured at Noise Measuring chamber accordance with standard. Therefore, these values depend on the ambient conditions
and values are normally higher in actual operation(Sound Pressure : LG Internal standard, Sound Power : EN 12102 (ISO 3741).
4. Capacities are net capacities and based on the following conditions. Refer to the Outdoor Unit Specifications for calculating the real capacity.
• Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
• Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
• Interconnected Pipe is standard length and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.