MULTI/SINGLE
Indoor unit
8. Installation
18
Ceiling Mounted cassette 4-way
CAUTION
• If the temperature rise above 30
or the humidity rise above RH 80%, the dew-protective kit should be equipped
or use additional insulation to the indoor unit body.
– "Dew Protective kit" is sold separately.
– Use the glass wool material or polyethylene foam and it make sure to be thick of 10mm at least.
TQ/TR Chassis
* According to product type,
model line up, sales
region..etc, applicability of
each chassis could be
different.
TP/TP-B Chassis
* According to product type,
model line up, sales
region..etc, applicability of
each chassis could be
different.
TM/TM-A/TN Chassis
* According to product type,
model line up, sales
region..etc, applicability of
each chassis could be
different.
Ceiling
Ceiling Board
Ceiling Board
Floor
Unit:mm(inch)
At least 1800(70-7/8)
3600(141-23/32) or less
1000(39-3/8)
or more
10(13/32)
or more
500(19-11/16)
or more
30(1-3/16)
±3(1/8)
500(19-11/16)
or more
300(1
1-
13
/16) or less
Ceiling
Ceiling Board
Ceiling Board
Floor
Unit:mm(inch)
At least 1800(70-7/8)
3600(141-23/32) or less
1000(39-3/8)
or more
10(13/32)
or more
500(19-11/16)
or more
15(19/32)
±3(1/8)
500(19-11/16)
or more
300(1
1-
13
/16) or less
Ceiling
Ceiling Board
Ceiling Board
Floor
Unit:mm(inch)
At least 1800(70-7/8)
4200(165-1
1/32) or less
1000(39-3/8)
or more
10(13/32)
or more
500(19-11/16)
or more
15(19/32)
±3(1/8)
500(19-11/16)
or more
300(1
1-
13
/16) or less