MPS Inverter SINGLE A
6. Electric Characteristics
Unit
Model
Type
MCA
MOP
MSC
RLA
kW
FLA
Voltage
Voltage range
Hz
Power
Compressor
OFM
AUUW126B
(UU12W UEB)
AUUW186B
(UU18W UEB)
AUUW246B
(UU24W UEB)
AUUW306B
(UU30W UEB)
AUUW366B
(UU36W UEB)
AUUW4860
(UU48W UYB)
AUUW6060
(UU60W UYB)
8.13
14.6
10
7.0
0.12
0.68
13.2
23.9
10
7.0
0.12
0.68
17.1
30.8
10/25
7.0/6.0
0.14
0.73
24.6
44.3
10/28
7.0/8.2
0.16
0.92
30.3
53.4
10/63
7.0/14.0
0.24
1.46
36.0
63.3
10/28/28 7.0/8.2/8.2
0.4
1.87
46.2
81.7
10/28/63 7.0/8.2/14.0
0.4
1.87
inverter
50
220~240
Min. : 198
Max. :264
Notes :
1. Voltage range
Voltage supplied to the unit terminals should be within the mini-
mum and maximum range
2. Maximum allowable voltage unbalance between phase is 2 %
3. MCA / MOP
MCA = (1.25 x Load1) + Load2 + Load3
MOP = (2.25 x Load1) + Load2 + Load3
- Load1 : Rated running current of largest motor
(compressor or other motor)
- Load2 : sum of current for all other motors
- Load3 : any other load rated 1.0A or more
4. Select wire spec. based on the MCA
5. Recommended circuit breaker is ELCB (Earth Leakage circuit
breaker)
6. MSC & RLA are measured as the compressor only test condi-
tion.
7. MSC values
10/28 : MSC of (inv. comp.) / (const. comp.)
8. RLA is measured during each individual compressor test condi-
tion.
Ex) 7.0/8.2 : RLA of (inv. comp.) / (const. comp.)
9. OFM is measured as the outdoor unit test condition
(Example) Selection of proper circuit breaker
Model : AUUW126B
- Rated running current : 6.5 A (refer to spec. sheet)
MCA = (1.25 x Load1) + Load2 + Load3
= (1.25 x 6.5) + 0 + 0 = 8.13 A
MOP = (2.25 x Load1) + Load2 + Load3
= (2.25 x 6.5) + 0 + 0 = 14.6 A
→
Finally select circuit breaker 15A(Min. circuit breaker is 15A)
MCA : Minimum Circuit Amperes (A)
MOP : Maximum rating over current protective device
MSC : Maximum Starting Current
RLA : Rated Load Amperes (A)
OFM : Outdoor Fan Motor
kW : Fan Motor rated output (kW)
FLA : Full Load Amperes (A)
Summary of Contents for ABNH186HLAB
Page 66: ...66 Universal System Air Conditioner II Outdoor Units Introduction 67 AUUW B AUUW 0 R410A 69 ...
Page 121: ...Electronic Control Device Service Manual 121 Ceiling Duct Type BH Series ...
Page 122: ...Electronic Control Device 122 Universal System Air Conditioner BG BR Series ...
Page 123: ...Electronic Control Device Service Manual 123 VE Series Ceiling Floor ...
Page 124: ...Electronic Control Device 124 Universal System Air Conditioner VB Series ...
Page 126: ...Schematic Diagram 126 Universal System Air Conditioner Ceiling Cassette Type ...
Page 127: ...Schematic Diagram Service Manual 127 Ceiling Duct Type ...
Page 128: ...Schematic Diagram 128 Universal System Air Conditioner Ceiling Floor ...
Page 183: ...P No 3828A22009B Printed in Korea ...