3.3 Inverter Protection control(2)
3.3.1 Function
: Power module failure protection by checking the temperature of heat sink.
There is a temperature sensor for checking the heat sink temperature.
3.3.2 Heat sink sensor failure error
Short Check : if temperature
≥
130°C
Open Check : if temperature < - 30°C
System will go in self diagnosis (error 65) is displayed and product stops.
3.3.3 Heat sink temperature control
a) Heat sink temperature < T2
: No limitation on compressor frequency
b) T2
≤
heat sink temperature < Toff : Compressor frequency down by 5 Hz
c) Heat sink temperature
≥
Toff
: Compressor will be off.
System will stop if this situation occurs 5 times in 1 hour and error code will be generated also self diagnosis will
start.
If high temperature situation occurs 5 times in 1 hr system counts 1 error and after that 4 times if this situation
occurs system stops and give error code.
If the temperature reached Toff condition system will count 5 times after that and system will stop with error
code.
COMP
Hz
Toff=85
°
C
T2=75
°
C
OFF
Set
frequency
Set
frequency
Set
frequency
Heat Sink temp
5 Hz
Down
5 Hz
Down
T1=70
°
C
Summary of Contents for ABNH186HLAB
Page 66: ...66 Universal System Air Conditioner II Outdoor Units Introduction 67 AUUW B AUUW 0 R410A 69 ...
Page 121: ...Electronic Control Device Service Manual 121 Ceiling Duct Type BH Series ...
Page 122: ...Electronic Control Device 122 Universal System Air Conditioner BG BR Series ...
Page 123: ...Electronic Control Device Service Manual 123 VE Series Ceiling Floor ...
Page 124: ...Electronic Control Device 124 Universal System Air Conditioner VB Series ...
Page 126: ...Schematic Diagram 126 Universal System Air Conditioner Ceiling Cassette Type ...
Page 127: ...Schematic Diagram Service Manual 127 Ceiling Duct Type ...
Page 128: ...Schematic Diagram 128 Universal System Air Conditioner Ceiling Floor ...
Page 183: ...P No 3828A22009B Printed in Korea ...