144 Universal System Air Conditioner
Outdoor Units
2.4 Oil equalizing control
2.4.1 Inv comp. Only : in heating & cooling
Operating condition :
1) When the continuous inverter compressor running time at under 25 Hz(option) is over 25 min.(option),oil restor-
ing operation is made.
2) If safety control device is operating under the 1) condition,this operation is not made.
3) During this operation,if operating Hz couldn’t be changed by safety control ,stop this operation.
Operating process :Once change the operating HZ to 50(option), and recover to the last value.
2.4.2 MPS system : in heating & cooling
Operating condition :
1) When the continuous inverter compressor running time at under 40 Hz(option) is over 2 hours(option) in 2 com-
pressor system, oil restoring operation is made.
2) If compressor operating Hz is below 40 Hz by the safety control, the accumulated time will be cleared and oil
restoration is not made.
3) During this operation,if operating Hz couldn’t be changed by safety control ,stop this operation.
Operating process : Raise the operating HZ up to 70,and after 20 sec.(option) recover to the last value.
Summary of Contents for ABNH186HLAB
Page 66: ...66 Universal System Air Conditioner II Outdoor Units Introduction 67 AUUW B AUUW 0 R410A 69 ...
Page 121: ...Electronic Control Device Service Manual 121 Ceiling Duct Type BH Series ...
Page 122: ...Electronic Control Device 122 Universal System Air Conditioner BG BR Series ...
Page 123: ...Electronic Control Device Service Manual 123 VE Series Ceiling Floor ...
Page 124: ...Electronic Control Device 124 Universal System Air Conditioner VB Series ...
Page 126: ...Schematic Diagram 126 Universal System Air Conditioner Ceiling Cassette Type ...
Page 127: ...Schematic Diagram Service Manual 127 Ceiling Duct Type ...
Page 128: ...Schematic Diagram 128 Universal System Air Conditioner Ceiling Floor ...
Page 183: ...P No 3828A22009B Printed in Korea ...