Ceiling & Floor
Service Manual 43
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power specially for the air conditioner. As for the method of
wiring, be guided by the circuit diagram pasted on the inside of control box cover.
2) Provide a circuit breaker switch between power source and the unit.
3) The screw which fasten the wiring in the casing of electrical fittings are liable to loose due to
vibrations to which the unit is subjected during the course of transportation. Check them and
make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of
the wires.)
4) Specification of power source
5) Confirm that electrical capacity is sufficient.
6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage
marked on the name plate.
7) Confirm that the cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.)
8) Never fail to equip a leakage breaker where it is wet or moist.
9) The following troubles would be caused by voltage drop-down.
• Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to
the normal function of a overload protection device.
• Proper starting power is not given to the compressor.
10) The means for disconnection from a power supply shall be incorporated in the fixed wiring and
have an air gap contact separation of at least 3mm in each active(phase) conductors.
CAUTION
Summary of Contents for ABNH186HLAB
Page 66: ...66 Universal System Air Conditioner II Outdoor Units Introduction 67 AUUW B AUUW 0 R410A 69 ...
Page 121: ...Electronic Control Device Service Manual 121 Ceiling Duct Type BH Series ...
Page 122: ...Electronic Control Device 122 Universal System Air Conditioner BG BR Series ...
Page 123: ...Electronic Control Device Service Manual 123 VE Series Ceiling Floor ...
Page 124: ...Electronic Control Device 124 Universal System Air Conditioner VB Series ...
Page 126: ...Schematic Diagram 126 Universal System Air Conditioner Ceiling Cassette Type ...
Page 127: ...Schematic Diagram Service Manual 127 Ceiling Duct Type ...
Page 128: ...Schematic Diagram 128 Universal System Air Conditioner Ceiling Floor ...
Page 183: ...P No 3828A22009B Printed in Korea ...