Service Manual 135
Ceiling & Floor
Ceiling & Floor
The function of main control
■
Soft-Dry Operation
• The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by microcontroller control.
■
Cooling Mode Operation
• When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote controller
and the operation diagram is as following.
Intake Air Temperature
SET TEMPE0.5°C
(Thermo. ON)
SET TEMPERATURE -0.5°C
(Thermo. OFF)
More than
More than
3 minutes
3 minutes
Selecting
Selecting
Selecting
fan speed
fan speed
fan speed
COMPRESSOR
ON
OFF
ON OFF
ON
INDOOR FAN
Low Low