16 Universal System Air Conditioner
Ceiling Cassette 4-way
Note :
1. Capacities are based on the following conditions:
Cooling: - Indoor Temperature 27°C(80.6°F) DB /19°C(66.2°F) WB
- Outdoor Temperature 35°C(95°F) DB /24°C(75.2°F) WB
Heating: - Indoor Temperature 20°C(68°F) DB / 15°C(59°F) WB
- Outdoor Temperature 7°C(44.6°F) DB / 6°C(42.8°F) WB
Piping Length - Interconnecting Piping Length 7.5m
- Level Difference of Zero.
2. Cooling/heating capacity of indoor unit can be lower when it is connected to MPS variable outdoor.
3. Wiring cable size must comply with the applicable local and national code.
3. Specifications
Power Supply
Ø/V/Hz
Cooling Capacity
kW
Btu/h
Heating Capacity
kW
Btu/h
Current
Nominal running current
A
Fan
Motor Type
Fan Type
Motor Output x Number of Unit
Air Flow Rate
cmm
(H/M/L)
cfm
Capacitor
µF/Vac
Drive
Coil
Row x Column x FPI
mm
Dimensions Body
mm(inch)
(WxHxD)
Decorative Panel
mm
Weight
Body
kg(lbs)
Decorative Panel
kg(lbs)
Air Filter
Sound Level (H/M/L)
dB(A)+3
Piping
Liquid
mm(inch)
Connections
Gas
mm(inch)
Drain(OD/ID)
mm
Dehumidification Rate
l/h
Safety devices
Temperature Sensor
Referigerant
Referigerant Control
Connectable outdoor unit
Power and transmission interunit cable
No.x mm
2
Model
ATNH126ELFB
[UT12 NEB]
ATNH186ELFB
[UT18 NEB]
ATNH246FLFB
[UT24 NFB]
ATNH306FLFB
[UT30 NEB]
Indoor unit type
Ceilling Cassette - 4way
1 / 220 ~240 / 50 1 / 220 ~240 / 50 1 / 220 ~240 / 50 1 / 220 ~240 / 50
3.52 5.28 7.03 8.21
12,000 18,000 24,000 28,000
4.04 5.95 8.09 9.44
13,800 20,300 27,600 32,200
0.35
0.43
0.53
0.67
Induction
Induction
Induction
Induction
Turbo Fan
Turbo Fan
Turbo Fan
Turbo Fan
18.4*1
22.4*1
40.3*1
48.6*1
9.5 / 8 / 7
13 / 12 / 11
15 / 14 / 13
19 / 17 / 15
336 / 283 / 247
459 / 422 / 388
530 / 494 / 459
671 / 600 / 530
2.5/440
2.5/440
4/440
4/440
Direct Drive
Direct Drive
Direct Drive
Direct Drive
2R x 11C x 19
2R x 11C x 19
2R x 11C x 19
2R x 12C x 21
570*269*570(22.4*10.5*22.4) 570*269*570(22.4*10.5*22.4) 744*292*744(29.3*11.5*29.3) 744*292*744(29.3*11.5*29.4)
670*30*670(26.4*1.2 *26.4)
670*30*670(26.4*1.2 *26.4)
850*30*850(33.5*1.2 *33.5)
850*30*850(33.5*1.2 *33.5)
19(41.9)
19(41.9)
24(52.9)
24(52.9)
3(6.6)
3(6.6)
3(6.6)
3(6.6)
Long life filter
Long life filter
Long life filter
Long life filter
38 / 35 / 32
41 / 39 / 37
43 / 41 / 39
45 / 42 / 39
6.35 (1/4)
6.35 (1/4)
6.35 (1/4)
6.35 (1/4)
9.52 (3/8)
12.7 (1/2)
12.7(1/2)
15.88 (5/8)
32 / 25
32 / 25
32 / 25
32 / 25
1.2
2.4
3
3.3
Fuse, Thermal protector for fan motor Fuse, Thermal protector for fan motor Fuse, Thermal protector for fan motor Fuse, Thermal protector for fan motor
Thermistor
Thermistor
Thermistor
Thermistor
R-410A
R-410A
R-410A
R-410A
Capillary
LEV
LEV
LEV
Single A
Single A
Single A
Single A
4*0.75
4*0.75
4*0.75
4*0.75
Conversion Formula
kW
= Btu/h
×
0.0002931
kcal/h = Btu/h
×
0.252
CFM = CMM
×
35.3
Summary of Contents for ABNH186HLAB
Page 66: ...66 Universal System Air Conditioner II Outdoor Units Introduction 67 AUUW B AUUW 0 R410A 69 ...
Page 121: ...Electronic Control Device Service Manual 121 Ceiling Duct Type BH Series ...
Page 122: ...Electronic Control Device 122 Universal System Air Conditioner BG BR Series ...
Page 123: ...Electronic Control Device Service Manual 123 VE Series Ceiling Floor ...
Page 124: ...Electronic Control Device 124 Universal System Air Conditioner VB Series ...
Page 126: ...Schematic Diagram 126 Universal System Air Conditioner Ceiling Cassette Type ...
Page 127: ...Schematic Diagram Service Manual 127 Ceiling Duct Type ...
Page 128: ...Schematic Diagram 128 Universal System Air Conditioner Ceiling Floor ...
Page 183: ...P No 3828A22009B Printed in Korea ...