Service Manual
93
Operation
1. MAIN UNIT FUNCTION
• DISPLAY
Operation Indicator
• On while in appliance operation, off while in appliance pause
• Flashing while in disconnection or short in Thermistor (3 sec off / 0.5 sec on)
Sleep Timer Indicator
• On while in sleep timer mode, off when sleep timer cancel or appliance operation pause
Timer Indicator
• On while in timer mode (on/off), off when timer mode is completed or canceled
Defrost Indicator
• Off except when hot start during heating mode operation or while in defrost control
■
Cooling Mode Operation
• When the intake air temperature reaches 0.5°C below the setting temp, the compressor and the outdoor fan
stop.
• When it reaches 0.5°C above the setting temp, they start to operate again.
Compressor ON Temp
➲
Setting Temp+0.5°C
Compressor OFF Temp
➲
Setting Temp-0.5°C
• While in compressor running, operating with the airflow speed set by the remote control. While compressor is
off fan operates at low speed regardless of the setting.
■
Soft Dry Operation Mode
• When the dehumidification operation input by the remote control is received, the intake air temperature is
detected and the setting temp is automatically set according to the intake air temperature.
26°C
≤
Intake Air Temp
➲
25°C
24°C
≤
Intake Intake Air Temp<26°C
➲
Intake Air Temp-1°C
18°C
≤
Intake Intake Air Temp<24°C
➲
Intake Air Temp-0.5°C
Intake Air Temp<18°C
➲
18°C
• While compressor off, the indoor fan repeats low airflow speed and stop.
• While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification
operation and 4-min compressor off repeat.
Compressor ON Temp.
➲
Setting Temp+0.5°C
Compressor OFF Temp.
➲
Setting Temp-0.5°C
• In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.
■
Heating Mode Operation
• When the intake air temp r3°…above the setting temp, the compressor is turned off. When below the
setting temp, the compressor is turned on.
Compressor ON Temp.
➲
Setting Temp.
Compressor OFF Temp.
➲
Setting Temp.+3°C
• While compressor on, the indoor fan is off when the indoor pipe temp. is below 20°C, when above 27°C , it
Function of control
Operation
Summary of Contents for A2UW146FA0
Page 143: ...Service Manual 143 Schematic Diagram 2 Art Cool Type ...
Page 144: ...144 Multi type Air Conditioner Schematic Diagram 3 Art Cool Deluxe Type A C MOTOR ...
Page 145: ...Service Manual 145 Schematic Diagram 3 Art Cool Deluxe Type BLDC MOTOR ...
Page 147: ...Service Manual 147 Schematic Diagram SLIM DUCT B1 B2 ...
Page 157: ...Service Manual 157 Schematic Diagram 15 SLIM DUCT B1 B2 ...
Page 161: ...Service Manual 161 Schematic Diagram 2 Art Cool Type TOP VIEW BOTTOM VIEW ...
Page 163: ...Service Manual 163 Schematic Diagram TOP VIEW BOTTOM VIEW 3 Art Cool Deluxe Type BLDC MOTOR ...
Page 165: ...Service Manual 165 Schematic Diagram Low static BT BT1 chassis ...
Page 166: ...166 Multi type Air Conditioner Schematic Diagram TOP VIEW BOTTOM VIEW Low static B1 B2 ...
Page 167: ...Service Manual 167 Schematic Diagram 5 Casset Type 1 way TC Chasis ...
Page 168: ...168 Multi type Air Conditioner Schematic Diagram 1 way TC1 Chasis TOP VIEW BOTTOM VIEW ...
Page 171: ...Service Manual 171 Schematic Diagram VB chassis ...
Page 172: ...172 Multi type Air Conditioner Schematic Diagram VB chassis TOP VIEW BOTOM VIEW ...
Page 175: ...Service Manual 175 Schematic Diagram 3 Outdoor Unit 1 Component side ...
Page 176: ...176 Multi type Air Conditioner Schematic Diagram 2 Solder side ...
Page 177: ...Service Manual 177 Schematic Diagram 3 Central control PCB 2 Bottom View 1 Top View ...
Page 268: ...P No 3828A20097W April 2006 Printed in Korea ...