Application information
Criterion
Limit value for
SPG operation
Remark
Interruption of the synchronization
beams
< 60 s
Protective field length only dependent on
ISO 13855.
Interruption of the transport flow
necessary
No
Distance from the transport mate-
rial to the protective device
< 200 mm
No additional measure necessary since it is not
possible to squeeze through between transport
material and protective device.
> 200 mm
Additional measure necessary, e.g., fencing or
wicket gates. The evaluation of the wicket gates
can be performed with operating mode 6 if neces-
sary (see chapter 4.4.4 "Operating mode 6 - Par-
tial gating").
Interruption of the two sensors
PS1 and PS2 is possible by a per-
son
No
Select a sufficiently large distance between the
sensors, e.g., 700 mm.
Protective-field filter time
2 s (operating
mode 1, operating
mode 6)
1 s (operating
mode 5)
0.5 s (operating
mode 4)
A brief clearing of the protective field is possible
without interruption of the gating event. Small
gaps in the transport material can thereby be tol-
erated (see chapter 4.1 "Overview and princi-
ple").
For a conveyor speed of 0.3 m/s, gaps of up to
300 mm are tolerated in operating mode 5
(1 s x 0.3 m/s = 300 mm).