Smart Process Gating
Leuze electronic GmbH + Co. KG
MLC 530 SPG
29
NOTICE
The timeout of 10 minutes can optionally be extended by another control signal (TH timer hold
signal) from the control to up to 100 hours (see chapter 4.5.2 "Gating timeout extension").
4.4.4
Operating mode 6 - Partial gating
The following functions are active in this operating mode (see chapter 8.5 "Operating mode 6"):
• Partial gating
• Qualified stop function
• MaxiScan
• Start/restart interlock active (see chapter 5.1 "Start/restart interlock RES")
The following functions can be selected as well:
• Gating timeout extension to up to 100 hours (see chapter 4.5.2 "Gating timeout extension")
• Fixed blanking can be taught with position tolerance of ± 1 beam (see chapter 5.5 "Blanking")
Like operating mode 1, operating mode 6 is intended primarily for lower conveyor speeds (< 0.1 m/s). For
an automatic gating end to be possible at speeds up to 0.1 m/s, t2 is set to 2 s.
Partial gating