PROFINET
Leuze electronic
DCR 248i
56
• Device naming
• Configuration of the device name
• Device naming
• Assigning the device names to the configured IO devices
• Assignment of MAC address – IP address – individual device names
• Checking device names
Start code reader
Ä
Connect the +18 … +30 V DC supply voltage (typ. +24 V DC).
ð
The code reader starts up.
Prepare the control
Ä
Assign the IO controller (PLC-S7) an IP address.
Ä
Prepare the control for consistent data transmission.
Install the GSDML file
Ä
Download the corresponding GSDML file from the Leuze electronic homepage:
www.leuze.com
.
NOTICE
Alternatively, the GSDML file can be loaded from the device with the webConfig tool (see chap-
ter 9 "Commissioning – Leuze electronic webConfig tool"):
HOME > INSTALLATION > GSDML file
The GSDML file stored in the device is always compatible with the firmware version of the
DCR 248i.
NOTICE
Do not change the GSDML file!
The GSDML file is a certified and integral part of the device and must not be changed. The file is
not changed by the system either.
If parameters are changed in the project tool, for example, these changes are stored by the con-
trol in the project, not in the GSDML file.
Ä
Install the GSDML file for the subsequent configuration of the code reader.
Configure the control hardware (S7 PLC)
Ä
Insert the code reader in your project. The PROFINET system is configured with the help of the hard-
ware configuration (HW-Config) of the SIMATIC Manager.
Ä
Assign an IP address a unique device name.