Device parameters and interfaces
Leuze electronic
AMS 200
75
TNT
3
5/7-2
4
V
8
.1.6.17 Module 17: SSI interface
Description
The module defines the parameters for the SSI interface.
Attention
!
The SSI interface can only represent positive distance values. If negative output val-
ues are ascertained due to the offset or count direction, a zero value is output at the
SSI interface
!
In the event of a number overflow, all data bits are set to "1".
The
unit
,
offset
and
count direction
parameters of module 1 also apply to the SSI inter-
face.
Notice
!
If the SSI interface is not configured via module 17 (SSI interface) in PROFIBUS oper-
ation, the SSI interface is deactivated.
If the SSI interface is operated without PROFIBUS (PROFIBUS OFF/SSI ON), configuration
is performed via the display.