Unidrive M200-201 Quick Start Guide
Issue Number: 7
Figure 3-1 Feature diagram (size 2 shown)
4
Electrical installation
An overlay of the electrical connections / terminals is included on the back page of this manual.
4.1 AC supply requirements
Voltage:
100 V drive: 100 V to 120 V ±10 %
200 V drive: 200 V to 240 V ±10 %
400 V drive: 380 V to 480 V ±10 %
Number of phases: 3
Maximum supply imbalance: 2 % negative phase sequence (equivalent to 3 % voltage imbalance
between phases).
Frequency range: 45 to 66 Hz.
For UL compliance only, the maximum supply symmetrical fault current must be limited to 100 kA.
On the size 2 110 V drives or when connecting single phase to a dual rated 200 V unit, the
supply should be connected to L1 and L3. Also the DC bus (-) terminal on 110 V drives
has no internal connection. The 110 V drives use a voltage doubler circuit on the input,
therefore the default for
Motor Rated Voltage
(Pr
08
) is 230 V.
5
7
8
4
6
11
1
3
2
10
9
2
3
12
Key
1. Rating label (On side of drive)
2. Identification label
3. Relay connections
4. Control connections
5. Braking terminal
6. Internal EMC filter screw
7. DC bus +
8. DC bus -
9. Motor connections
10. AC supply connections
11. Ground connections
12. Option module connection