Unidrive M200-201 Quick Start Guide
33
Issue Number: 7
This parameter changes the functions of the input terminals which are normally associated with the
enabling, starting and stopping the drive.
Action will only occur if the drive is inactive. If the drive is active, the parameter will return to its pre-
altered value on exit from edit mode.
Defines the reference when jog is enabled.
Defines the mode of analog input 1.
11
Start/Stop Logic Select
RW
Num
US
OL
Ú
0 to 6
Ö
0
RFC-A
Pr 11
Terminal 11
Terminal 12
Terminal 13
Latching
0
Enable
Run Forward
Run Reverse
No
1
/Stop
Run Forward
Run Reverse
Yes
2
Enable
Run
Forward/Reverse
No
3
/Stop
Run
Forward/Reverse
Yes
4
/Stop
Run
Jog Forward
Yes
5
User programmable
Run Forward
Run Reverse
No
6
User programmable
User programmable
User programmable
User programmable
15
Jog Reference
RW
Num
US
OL
Ú
0.00 to 300.00 Hz
Ö
1.50 Hz
RFC-A
16
Analog Input 1 Mode
RW
Txt
US
OL
Ú
4-20.S (-6), 20-4.S (-5), 4-20.L (-4),
20-4.L (-3), 4-20.H (-2), 20-4.H (-1),
0-20 (0), 20-0 (1), 4-20.tr (2),
20-4.tr (3), 4-20 (4), 20-4 (5), Volt (6)
Ö
Volt (6)
RFC-A