Unidrive M200-201 Quick Start Guide
35
Issue Number: 7
This parameter and
Status Mode Parameter 1
(Pr
23
) define which parameters are displayed in
Status mode. The values can be alternated by pressing the Escape key, if the drive is running.
See
Status Mode Parameter 2
(Pr
22
).
This parameter defines the scaling applied to
Status Mode Parameter 1
(Pr
23
). The scaling is only
applied in the Status mode.
If any number other than 0 is programmed into this parameter, user security can be applied so that
no parameters except Pr
10
can be adjusted with the keypad. When this parameter is read via a
keypad it appears as zero. Refer to the
Control User Guide
for further information.
Defines which value of keypad control mode reference is displayed at power-up.
22
Status Mode Parameter 2
RW
Num
PT
US
OL
Ú
0.000 to 30.999
Ö
4.020
RFC-A
23
Status Mode Parameter 1
RW
Num
PT
US
OL
Ú
0.000 to 30.999
Ö
2.001
RFC-A
24
Customer Defined Scaling
RW
Num
US
OL
Ú
0.000 to 10.000
Ö
1.000
RFC-A
25
User Security Code
RW
Num
ND
PT
US
OL
Ú
0-9999
Ö
0
RFC-A
27
Power-up Keypad Control Mode Reference
RW
Txt
US
OL
Ú
rESEt (0), LASt (1), PrESEt (2)
Ö
rESEt (0)
RFC-A
Value
Text
Description
0
rESEt
Keypad reference is zero
1
LASt
Keypad reference is the last used value
2
PrESEt
Keypad reference is copied from
Preset Reference 1
(Pr
18
)