CDC - START
console
54
• Electronic power circuit supply voltage is
less than :
- 177V if using the 230V input,
- 340V if using the 400V input.
• Restart requested before the time delay
has elapsed :
- Wait for the end of the time delay and
repeat the start command. (See protection
settings).
• Open circuit between terminals 10 and
11 of the STV 2313 remote control
terminal block.
• Communication between the STV and
the console is not possible.
• With the ES - START option, open
contact between terminals 11 (EL1) and
12 (0V) of the ES - START module.
• With the ES - START option, open
contact between terminals 13 (EL2) and
12 (0V) of the ES - START module.
F A U L T
M A I N S
S U P P L Y
F A U L T
T O O
M A N Y
S T A R T S
F A U L T
E M E R G E N C Y
S T O P
• With the ES - START option, the tripping
threshold of one of the PTC sensors
connected to terminals 3 to 7 of the ES -
START module is exceeded.
•
With the ES - START option, the
analogue input is outside the range
defined by the high and low levels. (See
protection settings).
• With the RV - START option, loss or ab-
sence of speed feedback.
This fault does not trip the STV 2313.
F A U L T
S E R I A L
L I N K
F A U L T
E X T .
T R I P
N
°
1
F A U L T
E X T .
T R I P
N
°
2
F A U L T
P T C
S E N S O R S
F A U L T
A N A L O G .
I N P U T
F A U L T
S P E E D
F E E D B A C K
Page: 54