CDC - START
console
47
Remarks
Selects the assignment of relay K2.
GENERAL FAULT : Relay open at a fault or if the electronic power circuit is off.
Note : ALARM ANALOG. I/P can only be accessed if the analog input has been
validated in menu 6.
If K2 = MOTOR STATUS : Select the operating phase to be monitored.
ENERGIZED
: Relay K2 closes as soon as the start command is given and opens
when the motor is switched off.
ACCELERATING
: Relay K2 closes as soon as the start command is given and opens
when the motor is at full voltage.
START COMPLETE : Relay K2 closes as soon as the start is complete (when the motor is
at full voltage) and opens as soon as the stop command is given.
If K2 = OVERLOAD
: Relay K2 closes when the power consumption is greater than
the closing threshold for a period longer than or equal to the
time delay.
It opens as soon as the power consumption falls below the
opening threshold.
If K2 = UNDERLOAD
: Relay K2 closes when the power consumption is less than
the closing threshold for a period longer than or equal to the
time delay.
It opens as soon as the power consumption is greater than
the opening threshold.
If K2 = ALARM ANALOG I/P
: Relay K2 closes when the analogue input level is greater
than the closing threshold for a period greater than or
equal to the time delay.
It opens as soon as the analogue input level falls below the
opening threshold.
Remarks
Once the parameters have been saved in the STV 2313 memory, it is possible to transfer
them to the console so that they may be copied at a later date to another STV 2313 with the
same power rating (see procedure in Section 3.7).