9
PROFINET communication
9.8
Parameterising the counter
531
Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Parameter data
Data set
Name
Description/value
Lenze
No.
Byte
0x00 0
Diagnostics
A diagnostic alarm occurs if the same event triggers a further
process alarm during a process alarm processing.
Bit 5 ... 0: Reserved
Bit 6: Diagnostic alarm(0 = inhibited; 1 = enabled)
Bit 7: Reserved
Other values are not permissible!
0x00
0x01 0
Input frequency
Track A
Filters for instance serve to filter signal peaks in the case of
an unclean input signal.
0 (0x00): 500 kHz
1 (0x01): 300 kHz
2 (0x02): 100 kHz
3 (0x03): 60 kHz
4 (0x04): 30 kHz
6 (0x06): 10 kHz
7 (0x07): 5 kHz
8 (0x08): 2 kHz
9 (0x09): 1 kHz
Other values are not permissible!
0x02
1
Input frequency
Track B
0x02
2
Input frequency
Reset
0x02
3
Reserved