9
PROFINET communication
9.2
Access to the I/O system 1000
469
Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.2.1
Access to the I/O area
With PROFINET, the input/output range is automatically shown in the corresponding address range
of the master system. The following index no. also provides access to the I/O ranges:
• Index = 0x8028: Reading of the input data (slot 1 ... 64)
• Index = 0x8029: Reading of the output data (slot 1 ... 64)
9.2.2
Access to parameter data
The GSDML file serves to set parameter data for the corresponding modules via the hardware
configuration. When the I/O device starts, the parameter data is given once to the modules via the
I/O controller. After writing, the parameter data in the module is active.
Access to
Slot
Index
All parameters of the PROFINET coupler incl. header (4 bytes)
0
0x007D
All parameters of the PROFINET coupler
0
0x007E
All module parameters incl. header (4 bytes)
1 ... 64
0x007D
Data record DS 0x00 of the module parameters
1 ... 64
0x007E
Data record DS 0x01 of the module parameters
1 ... 64
0x007F
Data record DS 0x80 ... 0x90 of the module parameters
1 ... 64
0x0080 ...0x0090