5
CANopen communication
5.19
Diagnostics
181
Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.19
Diagnostics
The following indices can be used for purposes of diagnostics. They show operating states. Settings
cannot be made.
5.19.1
Emergency telegram
By means of the emergency telegram, the I/O system communicates internal device errors to other
system bus nodes with high priority. 8 bytes of user data are available.
Emergency telegram structure
Note!
The diagnostic function is only supported by I/O compound modules from HW version
1B and by bus coupler modules from HW version 1A.
If a module in the system complies with an earlier HW version, the diagnostic function
is deactivated for all modules.
Index
Information displayed
I-1014
Emergency telegram
I-1027
Reading out the module IDs
I-6000
Status of digital inputs
I-6200
Status of digital outputs
I-6401
Status of analog inputs
I-6411
Status of analog outputs
I-5400 ...
I-5403
Counter status
I-1003
Current errors
Index
Name
Possible settings
Info
Lenze
Selection
I-1003
Read only, fault memory
1 Actual errors
I-1014
COB ID emergency
Emergency telegram
After the boot-up, the identifier
0x80 + node address are displayed.
Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
LOW byte
HIGH byte
Error register
I-1001
Error information
Error code
Error code
The error code 0x81
(device error) is
displayed in the index
I-1001 (error register).
1
2
3
4
5