DeviceNet communication
8.8
Parameterising technology modules
459
Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Option 4 / 5, TMO
9
TMO (HIGH byte)
TMO serves to define the maximally permissible interval
between two frames.
0 ... 65535 [ms] (0x0000 ... 0xFFFF)
0x00
10
TMO (LOW byte)
0xFA
Option 6, number of start identifiers
10
Number of start
identifiers
0x00: 1 start identifier (2. start identifier is ignored)
0x01: 2 start identifiers
0x01
Option 7, start identifier 1
11
Start identifier 1
ASCII value of the initial character that is sent in advance of
a frame and marks the start of a transmission.
0 ... 255 (0x00 ... 0xFF)
0x00
Option 8, start identifier 2
12
Start identifier 2
ASCII value of the initial character that is sent in advance of
a frame and marks the start of a transmission.
0x00
Option 9, number of end identifiers
13
Number of end
identifiers
0x00: 1 end identifier (2. end identifier (0x310D/x) is
ignored)
0x01: 2 end identifiers
0x00
Option 10, end identifier 1
14
End identifier 1
ASCII value of the end character that is sent after a frame and
marks the end of a transmission.
0 ... 255 (0x00 ... 0xFF)
0x00
Option 11, end identifier 2
15
End identifier 2
ASCII value of the end character that is sent after a frame and
marks the end of a transmission.
0 ... 255 (0x00 ... 0xFF)
0x00
Option 12, reserved
16
Reserved
0x00
Option 13, operating mode
17
Operating mode
The operating mode determines if the interface is to be
operated half duplex (RS485) or full duplex (RS422).
• 0x00: Half duplex - two-wire operation (RS485)
Half duplex operation means that either transmission or
reception can take place at a time. The data are
transmitted between the communication partners
alternately in both directions.
In case of the half duplex parametersetting under RS485,
no software data flow control is possible.
• 0x01: Full duplex - four-wire operation (RS422)
The data are exchanged simultaneously between the
communication partners; transmission and reception can
take place at the same time. Each communication partner
must simultaneously actuate a receive path.
0x01
Position in string Name
Description/value
Lenze
No.