
6
PROFIBUS communication
6.10
Parameterising technology modules
305
Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Diagnostic data
In the event of an error the corresponding channel LED of the module is lit and the error is entered
in the diagnostic data.
Diagnostic data record - data record 0x01
Name
Byte
Function
Default
ERR_A
1
ERR_A-diagnostics
Bit 0: Set in the case of module fault
Bit 1: Set in the case of internal error
Bit 2: Set in the case of external error (cable break)
Bit 3: Reserved
Bit 4: Set in the case of a missing external supply voltage
Bit 5, 6: Reserved
Bit 7: Set in the case of parameterisation error
0x00
MODTYP
1
Module information
Byte 0:
Bit 3 ... 0: Module class (0b0111: Gateway module)
Bit 4: channel information available
Bits 7 ... 4: 0 reserved
0x17
ERR_C
1
ERR_A-diagnostics
Bit 7 ... 0: Reserved
0x00
ERR_D
1
ERR_D diagnostics
Bit 3 ... 0: Reserved
Bit 4: Set in the case of internal communication error
Bit 7 ... 5: Reserved
0x00
CHTYP
1
Channel type
Bit 7 ... 0: Reserved
0x00
NUMBIT
1
Number of diagnostic bits of the module per channel (here
0x08)
0x08
NUMCH
1
Number of channels in module
Bit 7 ... 0: Reserved
0x00
CHERR
1
Bit 7 ... 0: Reserved
0x00
CH0ERR ... CH7ERR
8
Bit 7 ... 0: Reserved
0x00
DIAG_US
4
Value of
s ticker when diagnostics occur
Bytes 0 ...3
0x00