Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17
204
5
CANopen communication
5.20
Index table
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
1 COB-ID used by
TxPDO 7
704 +
NID
385
{1}
2047
Definition of specific identifiers for
process data object 7 (NID= Node
ID / node address)
2 Transmission type
255
0
{1}
255
Defining the transmission mode
0
Function deactivated
The output data are accepted on
sync telegram transmission.
1 ... 240 Process data transfer after sync no. 1
...
Process data transfer according to
sync no. 240
The output data is accepted after
the set number of sync telegrams
(1 ... 240) has been transmitted
254
Time-controlled process data
transfer
Only if a cycle time is set in I-180x,
subindex 5
255
Event-controlled process data
transfer
255
Event-controlled process data
transfer with cyclic overlay
Only if a cycle time is set in I-180x,
subindex 5
3 Inhibit time
0
0
{1 ms}
65535
Blocking time
5 Event time
0
0
{1 ms}
65535
Cycle time
I-1807
1 COB-ID used by
TxPDO 8
960 +
NID
385
{1}
2047
Definition of specific identifiers for
process data object 8 (NID= Node
ID / node address)
2 Transmission type
255
0
{1}
255
Defining the transmission mode
0
Function deactivated
The output data are accepted on
sync telegram transmission.
1 ... 240 Process data transfer after sync no. 1
...
Process data transfer according to
sync no. 240
The output data is accepted after
the set number of sync telegrams
(1 ... 240) has been transmitted
254
Time-controlled process data
transfer
Only if a cycle time is set in I-180x,
subindex 5
255
Event-controlled process data
transfer
255
Event-controlled process data
transfer with cyclic overlay
Only if a cycle time is set in I-180x,
subindex 5
3 Inhibit time
0
0
{1 ms}
65535
Blocking time
5 Event time
0
0
{1 ms}
65535
Cycle time
I-1808
Index
Name
Possible settings
Info
Lenze
Selection