CANopen
6
Parameter setting
6-46
L
BA2175 EN 2.0
6.5.2
Description of communication-relevant Lenze codes
6.5.2.1
L-C1810: Software product code
Possible settings
Code
Subcode
Index
Lenze
Selection
Data type
L-C1810
-
22765
d
= 58ED
h
-
-
VS
During module initialisation the bus devices are defined by means of the product code.
6.5.2.2
L-C1811: Software date
Possible settings
Code
Subcode
Index
Lenze
Selection
Data type
L-C1811
-
22764
d
= 58EC
h
VS
This date is mainly needed for service.
6.5.2.3
L-C1850/ L-C2350: Node address
Possible settings
Code
Subcode
Index
Lenze
Selection
Data type
L-C1850
-
58C5
h
= 22725
d
1
1
[1]
63 FIX32
L-C2350
-
56D1
h
= 22225
d
1
1
[1]
63 FIX32
This code can be used to set the 2175 module address via the CAN bus.
Code L-C1850 maps code L-C0009 of the basic unit. Writing to L-C1850 has a direct effect on
L-C0009.
Note!
This code is only effective if the DIP switches S1-S6 have been switched OFF before mains
switching.
A node address modification will only become active after power-on of the 2175 module or sending
of the network management command
Reset_node or Reset_communication via the CAN bus.
With 9300 servo PLCs it can also be modified by setting code C2120 (AIF control byte) to 1.